LST GIF8-1 Folheto

Página de 2
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
GIF8-1_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
The  Conventional  Detector  Interface  GIF8-1  supports 
eight detector zones in addressable conventional tech-
nology in Fire Detection Control Panels Series BC216. 
Up to 64 detectors (addresses) per detector line can 
be individually identifi ed with the aid of an address mo-
dule.
In the event of an alarm, the fi re detection control panel 
indicates the number of the detector that is activated 
fi rst and displays the optionally parameterised text in-
formation. Depending on the type of detector (manual 
call point, automatic fi re detector with or without alarm 
verifi cation, fault message contacts as well as contacts 
for  technical messages), the function of  the detector 
zone can be set separately for each detector line.
The Conventional Detector Interface provides a proces-
sor of its own. At a possible central processing board 
failure, the diversifi ed redundancy concept thus ensures 
reliable alarm recognition. Each input of the Conventio-
nal Detector Interface is protected against overvoltage 
and thus provides high system stability.
•   For the connection of 8 detector 
lines in addressable conventional 
technology
•   Individual detector addressing with 
optional address module
•   Individual setting of detector zone 
function
•   Lines monitored for wire breakage, 
short circuit, and short to earth