LST 4351E Folheto

Página de 1
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
4351E_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
The Thermal Max Detector 4351E recognises a maxi-
mum temperature of 78°C as sign of fi re. It complies 
with Class BS and can be used up to a room height 
of 6m.
Addressable conventional technology is used for alarm 
transmission  to  the  fi re  detection  control  panel.  The 
detector addressing can be achieved in 2 ways:
•   A detector with an Address Module NG58-1 can be 
individually identifi ed by the suitable control panel.
•   An address, which has been stored in the detector 
by means of the Remote Programming and Test Unit, 
is displayed on the Zonal Display Unit S300ZDU.
A  test  activation  of  the  detector  can  be  carried  out 
using the Remote Test Unit ECO1000RTU. In addition 
to the test activation of the detector, the Remote Pro-
gramming and Test Unit S300RPTU can also be used 
to set and display the following detector parameters:
•  the detector address, and
•  the date of the previous maintenance.
The detector can be attached to various detector ba-
ses and it can be protected against theft.
•   Addressable conventional technology
•   Alarm temperature 78°C
•   Addressing by means of address 
module or detector parameterisation
•   Remote readout of detector condition
•   Function testable with Remote Test 
Unit ECO1000RTU
Specifi cations
Operating voltage 
Supply through the detector line voltage
Current consumption 
typ. 85µA (quiescent)
Alarm temperature 
78°C
Ambient temperature 
-30°C to +70°C (continuous operation)
Relative humidity 
5 – 95% (no condensation)
Dimensions ø × H 
102 × 43 (mm)
Colour 
cream
Weight 
75g
Approval 
VdS G202016
Order number 
242041
Order name 
Thermal Max Detector/Conv./300/SS 4351E