LST 55000-847 Folheto

Página de 1
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
55000-847_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
The  addressable  Module  55000-847  serves  for  the 
line-monitored  integration  of  contact  detectors,  such 
as  manual  call  points,  sprinkler  system  contacts  or 
supervising contacts, into the bidirectional communica-
tion on the ADM loop with Apollo/Discovery protocol. 
Furthermore, it can be used to actuate external devices 
by means of a relay output with two dry change-over 
contacts, via the ADM loop. In addition to the monitored 
input and the relay output, the module has an opto-cou-
pled input for monitoring an external voltage.
The address is easily selected by means of a built-in DIL 
switch. Status LEDs indicate the condition of input and 
output. The module has an integrated dual-isolator and 
is fi tted into a plastic case.
•   ADM loop technology with
Apollo/Discovery protocol
•   One line-monitored input and one 
relay output with two dry contacts
•   Setting of module address by means 
of address switch
•  Integrated dual-isolator
•   Status LEDs for input and output
Specifi cations
Operating voltage 
Supply through loop voltage
Current consumption 
approx. 1.5mA (quiescent)
Contact rating 
1A/30VDC or AC
Ambient temperature 
-20°C to +70°C
Dimensions L × W × H 
150 × 90 × 48 (mm)
Colour 
white
Weight 
240g
Approval 
VdS G201032
Order number 
249076
Order name 