H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS
3
63-2579—3
WIRING
For voltage output, shielded cable (16-22 AWG) should 
be used.
For current output, either shielded cable or twisted pair 
(16-22 AWG) can be used.
NOTE: When using shielded cable, ground the shield 
only at the controller end (see Fig. 2). Grounding 
both ends can cause a ground loop.
The 20K ohm NTC temperature output is accessed 
through the separate blue and green wires (located inside 
the enclosure).
Fig. 2. Typical wiring diagram for transducer with two-
wire mA output and external DC power supply.
Fig. 3. Humidity sensor (0-10 Vdc output) wiring with T7350 
(use with RH/Temperature combination T7350 units only).
mA OUTPUT
TRANSDUCER
ONLY
18 TO 36 Vdc
POWER SUPPLY
CONTROLLER, METER 
OR RECORDER
INPUT SIGNAL
COMMON
Vin
+
+
Io
M22528
GROUND
POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD.
HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER.
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
HC AND HP PROVIDE 24 VAC TO THE HUMIDITY SENSOR.
1
M22529
2
3
2
3
4
5
5
RC
X
T7350
SUBBASE
W1
G
T7770 REMOTE SENSOR
Y1
W3/Y4 Y3
W2
Y2
AUX
RH
T5
T6
T7
T4
T3
DISCHARGE
AIR
SENSOR
OUTDOOR
AIR
SENSOR
MOTION
SENSOR
HUMIDITY SENSOR
M
OS
OS
AS
AS
M
HC
HP
HS
Gnd
Vin
(Vac)
Vo
(0-10 Vdc)
1
4
L1
(HOT)
L2
COMPRESSOR
CONTACTOR 1
COMPRESSOR
CONTACTOR 2
HEAT
RELAY 1
1
2
3
4
5
6
7
8
9
FAN
RELAY
ECONOMIZER
HEAT
RELAY 2
COMPRESSOR
CONTACTOR 3
COMPRESSOR
CONTACTOR 4