Honeywell H7635C Manual Do Utilizador

Página de 8
H7625B; H7635B,C; H7655B DUCT-MOUNT AND OUTDOOR-MOUNT HUMIDITY/TEMPERATURE SENSORS
63-2579—3
6
APPENDIX
RH Test and Configuration DIP Switch Settings (Table 3)
IMPORTANT
• Only adjust these switches for troubleshooting or 
recalibrating the sensor. (Adjustment is not 
normally necessary.)
• For normal operation, always keep DIP switch 3 
in the ON position. When DIP switch 3 is off, the 
RH transmitter cannot read the sensor. This 
inability-to-read forces the output to never 
change.
Table 3. Test/Calibration Settings (Six-Switch Block).
0% RH Output (for Testing Only)
Transmitter always outputs a signal of 4 mA or 0 Vdc. The 
sensor does not affect the transmitter output.
50% RH Output (for Testing Only)
Transmitter always outputs a signal of 12 mA, 2.5 VDC, or 
5 VDC. The sensor does not affect transmitter output.
100% RH Output
Transmitter always outputs a signal of 20 mA, 5 VDC, or 
10 VDC. The sensor does not affect the transmitter 
output. Sensor doesn’t affect the transmitter output.
Normal Operating Condition
DIP switch 3 must be set in the On position for normal 
operation. All other DIP switches must be set Off.
Setting
6
5
4
3
2
1
Normal Operation (Default)
— — — On — —
0%  RH  Output
On — — — — —
50%  RH  Output
— On — — — —
100% RH Output
— — On — — —
Increment RH Output
— — — — On —
Decrement  RH  Output
— — — — — On
Reset to Original Calibration
— — — — On On