Model FSD-M211 meets the requirements for fire 
dampers, smoke dampers and combination fire 
smoke dampers established by:
National Fire Protection Association 
    NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC  International Building Codes
ICBO  Uniform Building Codes  
SBCCI  Standard Building Codes
British Standard BS476
Tested to 4 hours at Warrington Fire, UK
Application
Model FSD-M211 is a combination fire smoke damper with 3V style 
blades. The FSD-M211 has been qualified to 10.2 m/s and 1 kPa for 
operation and dynamic closure in emergency fire smoke situations. 
Model FSD-M211 may be installed vertically (with blades running 
horizontal) or horizontally and is rated for airflow and leakage in 
either direction.
Model FSD-M211 has also been tested in accordance with BS476 to 
4 hours at Warrington Fire, UK, and is approved for fire partitions of 
4 hours or less where British Standards are required.
Ratings
UL 555 Fire Resistance Rating
 
Fire Rating: 
1
1
2
 Hours
 
Dynamic Closure Rating: Actual ratings are size dependant
 
Maximum Velocity: 
10.2 m/s
 
Maximum Pressure: 
1 kPa
UL 555S Leakage Rating
 
Leakage Class: 
I
 
Operational Rating: Actual ratings are actuator dependant
 
Maximum Velocity: 
10.2 m/s
 
Maximum Pressure: 
1 kPa
 
Max.  Temperature:    
177°C —Depending on actuator
BS476 Fire Resistance Rating
 
Fire Rating: 
4 hours
Standard Construction
 
Frame: 
 
127mm x 25mm galv. steel hat 
 
channel with reinforced corners . A 
 
low profile head and sill are used on 
 
sizes less than 432mm high to 
 
maximize free area and 
 
performance. 
 
Blades: 
1.5mm galvanized steel, reinforced 
 
 
with 3 longitudinal structurally 
 
 
designed vee’s. 
 
Seals: 
Extruded silicone rubber blade 
 
 
seals. Flexible stainless steel jamb 
 
 
seals. 
 
Closure Device: 
74°C RRL  
 
Linkage: 
Concealed in jamb. 
 
Axles: 
13mm diameter plated steel 
 
Bearings: 
Bronze sleeve type.
Size Limitations
 
Minimum Size: 
101mm  W x  101mm H 
 
Maximum Size: 
 
Single Section:  
813mm W x 1270mm H 
 
 
or 914mm W x 914mm H 
 
Multiple Section: 
3251mm W x 2540mm H Vertical 
 
 
or 3658mm W x 2438mm H 
 
 
Horizontal
Optional Features
• Stainless steel bearings 
• 100°C, and 177°C RRL  available (UL only) 
• 69°C fusible link (BS476) 
• Electric or pneumatic actuators to accomplish smoke 
   management and system functions. 
• Sleeve with Integral flange on both sides available 
• RRL/OCI (open close indication) 
• TOR (remote override of 74°C or 100°C closure allows damper to 
   perform smoke management functions during a fire emergency)
Model FSD-M211
Steel 3V Blades
UL 555S Leakage Class I
UL555 1
1
2
 Hour Fire Resistance Rating
4 Hour Fire Resistance Rating (BS476)
Combination 
FIRE SMOKE DAMPERS
* W & H dimensions furnished approximately 6mm undersize.
  (Add sleeve thickness for overall sleeved damper dimension)
  Right hand drive is shown. Left hand drive is available upon request.
H
W
LH
RH
“UL CLASSIFIED (see complete marking on 
product)”
“UL CLASSIFIED to Canadian safety standards 
(see complete marking on product)”
 
Standard 555 & 555S (Listing #R13317)
Greenheck Kunshan Co. Ltd. and Greenheck Fan 
Corporation certifies that the model FSD-M211 
shown herein is licensed to bear the AMCA Seal. The 
ratings shown are based on tests and procedures 
performed in accordance with AMCA Publication 
511 and comply with the requirements of the AMCA 
Certified Ratings Programs. The AMCA Certified 
Ratings Seal applies to air performance ratings only. 
®
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
AIR
PERFORMANCE
Installation instructions available at www.greenheck.com