Greenheck Fan none Manual Do Utilizador

Página de 3
Part number 465915
 
Installation Instruction Supplement for 
SMD, SESMD, & SSSMD
 Series
Smoke Dampers and
FSD, FSD-3XXV, SEFSD, & SSFSD
 
Series
Combination Fire Smoke Dampers 
with Factory Mounted No Flow Duct Smoke Detectors
UL CLASSIFIED (see complete marking on product)
UL CLASSIFIED to Canadian safety standards (see 
complete marking on product)
 
Standard 555 (Listing #R13317)
 
Standard 555S (Listing # R13447)
Refer to:
‘Installation Instructions for SMD, SESMD, and 
SSSMD Series Leakage Rated Smoke Dampers’ 
(Part #461338)
or
‘Installation Instructions for CFSD, FSD, DFD, 
SEFSD, SSFSD Series Combination Fire Smoke 
Dampers’ and (Part#461336) and FSD-3XXV series 
(Part #461666) for additional details
NOTES
1. Minimum air velocity for smoke detector operation is 
    0 fpm. Maximum is 3000 fpm.
2. Model 2151 low profile smoke detector is mounted to a 
    standard electrical box within the duct. The twist-in/
    twist-out head allows easy removal from the base for 
    quick cleaning and maintenance. 
3. Smoke detector specifications are:
    Operating temperature rating: 32°F to 120°F (0°C to 49°C)
          Operating humidity range: 10% to 93% RH
                       Operation voltage: 120 VAC
4. Refer to System Sensor, 2151, Installation and Maintenance
    Instructions for further installation details. 
5. Refer to System Sensor, 2151, Installation and Maintenance
    Instructions for maintenance and field tests.
6. System Sensor
    3825 Ohio Avenue
   St. Charles, IL 60174
   Phone: 1-800-736-7672
   Fax:  1-630-377-6495
   Website: www.systemsensor.com
#10 TEK SCREW
4 X 4 X 2 1/8 HANDI BOX
SMOKE DETECTOR ASSEMBLY