Greenheck Fan SMD-401M Manual Do Utilizador

Página de 4
Model SMD-401M meets the requirements for smoke 
dampers established by: 
National Fire Protection Association 
    NFPA Standards 92A, 92B, 101 & 105
IBC International Building Codes
ICBO Uniform Building Codes
New York City (MEA listing #260-91-M)
CSFM California State Fire Marshal
    Leakage (Smoke) Damper Listing  (#3230-0981:108)
“UL CLASSIFIED (see complete marking on 
product)”
“UL CLASSIFIED to Canadian safety standards 
(see complete marking on product)”
 
Standard 555S (Listing #R13317)
APPLICATION
Model SMD-401M is a class I leakage rated modulating smoke 
damper. The model SMD-401M serves the function of 
both a control damper and smoke damper. High strength airfoil 
blades ensure the lowest resistance to airflow in HVAC systems 
with velocities to 2000 fpm (10.2 m/s ) and 4 wg (1 kPa). Model 
SMD-401M may be installed vertically (with blades running 
horizontal) or horizontally and is rated for airflow and leakage in 
either direction.
RATINgS
 
Leakage Class: 
Operational Rating: Actual ratings are size dependent. 
 
Max. Velocity: 
up to 2000 fpm (10.2 m/s) 
 
Max. Pressure: 
4 in. wg (1 kPa) 
 
Temperature: 
250°F (121ºC) with all actuators.
STANDARD CONSTRUCTION
 
Frame:  
5 in. x 1 in. (127mm x 25mm) 
 
 
galvanized steel hat channel with 
 
 
reinforced corners. A low profile 
 
 
head and sill are used on sizes 
 
 
less than 17 in. (432mm) high to 
 
 
maximize free area and 
 
 
performance. 
 
Blades:  
Airfoil shape constructed of 
 
 
heavy gauge extruded aluminum. 
 
 
Structural reinforcement through 
 
 
the entire length. 
 
Seals: 
Extruded silicone rubber blade 
 
 
seals. Flexible stainless steel 
 
 
jamb seals. 
 
Linkage: 
Concealed in jamb. 
 
Axles: 
1
2
 in. (13mm) dia. plated steel. 
 
Bearings: 
Bronze sleeve type.
SIzE LIMITATIONS:
 
Minimum Size: 
8 in. W x 8 in. H 
 
 
(203mm W x 203mm H) 
 
Maximum Size: 
 
Single Section: 
36 in. W x 36 in. H 
 
 
(914mm W x 914mm H)
 
Multi Section: 
144 in. W x 36 in. H 
 
 
(3658mm W x 914mm H)
Optional Features:
• Galvanized steel sleeves.
• Stainless steel bearings
• OCI (Open closed indication switches)
•  Electric or pneumatic actuators to accomplish smoke 
management and system functions.
• POC Retaining angles 
• Smoke detector
• Momentary switch
• Transitions (R, C, O)
• Sealed transitions and sleeves
SMD-401M
Smoke Dampers
Extruded Airfoil Blades
UL 555S Leakage Class I
*W&H dimensions furnished approximately 
1
/
4
 in. (6mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
H*
W*
LH
RH
Installation instructions available at www.greenheck.com