Greenheck Fan SEFSDR-511 Folheto

Página de 2
* Dimensions furnished approximately 1/8 in. (3mm) undersize.
D*
Model SEFSDR-511 meets the requirements for fire 
dampers, smoke dampers and combination fire smoke 
dampers established by:
National Fire Protection Association 
    NFPA Standards 80, 90A, 92A, 92B 101 & 105
IBC  International Building Codes
New York City (MEA listing #260-91-M) 
California State Fire Marshall
    Listing #: 3225-0981:112 (fire)
     Listing #: 3230-0981:113 (smoke)
Application
Model SEFSDR-511 is a severe environment 316SS combination fire 
smoke damper with round style blade. The SEFSDR-511 has been 
qualified to 3000 fpm (15.2 m/s) and 4 in. wg (1 kPa) for operation 
and dynamic closure in emergency fire smoke situations. Model  
SEFSDR-511 may be installed vertically (with blades running 
horizontal) or horizontally and is rated for airflow and leakage in 
either direction.
Ratings
UL 555 Fire Resistance Rating 
 
Fire Rating:  1 1/2 Hour 
Dynamic Closure Rating: Actual ratings are size dependant 
 
Maximum Velocity:  3000 fpm (15.2 m/s) 
 
Maximum Pressure:  4 in. wg (1 kPa)
UL 555S Leakage Rating 
 
Leakage Class:  I 
 
Operational Rating:  Actual ratings are actuator dependant 
 
Maximum Velocity:  3000 fpm (15.2 m/s) 
 
Maximum Pressure:  4 in. wg (1 kPa)
 
 
 
Maximum Temperature:  350º F (177°C) —Depending on actuator
Standard Construction
 
Frame/Sleeve:  20 ga. (1mm) 316 stainless steel integral 
 
  sleeve 
 
Blade:  Double skin 316 stainless steel (14 ga. 
 
  [2mm] equivalent) round style blade 
 
Seal:  Extruded silicone rubber blade seal 
 
Axle:  1/2 in. (13mm) dia. 316 stainless steel 
 
Bearing:  316 stainless steel sleeve type 
 
Fusible Link:  UL listed 165ºF (74ºC) -not 316SS
Size Limitations
 
Minimum Size:  6 in. (152mm) diameter 
 
Maximum Size:  24 in. (610mm) diameter
Optional Features
• OCI (Open closed indication switches) -not 316SS
• 165ºF (74°C), 212ºF (100°C), and 350ºF (177°C) RRL - not 316SS.
• TOR (remote override of 165º F (74°C) closure allows damper to
perform smoke management functions during a fire emergency) -not 
316SS.
• Electric or pneumatic actuators to accomplish smoke management
and system functions.
 
• One retainer plate required, additional retainer plate available
• 14 ga. (2mm) or 16 ga. (1.5mm) frame/sleeve
SEFSDR-511
Combination Fire Smoke Dampers
Round Stainless Steel Blade
UL 555S Leakage Class I
UL555 1 1/2 Hour Fire Resistance Rating
“UL CLASSIFIED (see complete marking on 
product)”
“UL CLASSIFIED to Canadian safety standards 
(see complete marking on product)”
 
Standard 555 (Listing #R13317)  
 
 
Standard 555S (Listing #R13447)
Opening + 2 in.  Min.
1.00 in. Min. Typ.
Fasteners
Clamping
Screw
Nut
Retaining
Plate Assembly
Clamping Screw
Minimum Wall/Floor Opening
 = Nominal Dia. + 7/8 in. 
Opening + 2 in.  Min.
1.00 in. Min. Typ.
Fasteners
Clamping
Screw
Nut
Retaining
Plate Assembly
Clamping Screw
Minimum Wall/Floor Opening
 = Nominal Dia. + 7/8 in. 
Installation instructions available at www.greenheck.com.