Honeywell IPGSM-DPC Manual Do Utilizador
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide
– 1 –
General Information
The IPGSM-DPC Commercial Fire Communicator (henceforth referred to as IPGSM-DPC) includes
everything you need to upgrade a commercial fire system that previously reported by POTS to a system that
everything you need to upgrade a commercial fire system that previously reported by POTS to a system that
uses the Internet as its primary reporting path, and uses a GSM cellular reporting path as a backup. In
addition, this communicator utilizes a sophisticated power module (PowerBoost1) that monitors and reports
AC power loss, low battery, and missing battery conditions.
AC power loss, low battery, and missing battery conditions.
Package Contents
Red Fire Cabinet and Back Plate
Antenna and Mounting Adapter
Mounting Rails (for above)
Cam Lock with Key
PowerBoost1
Hardware Bag
Dialer Capture Module
Battery harness/fuse (# 100-02415)
Transformer, 18VAC
iGSM Communications Module
Ferrite Filter
(# 1451-UL9)
50 ohm cable assembly
LED Display board
Compatible Fire Panels
The IPGSM-DPC works with:
All Fire Panels that are listed in the table below.
All Fire Panels that use the Contact ID communication format as described in the SIA DC-05
Standard.
IMPORTANT: For a fire panel that has more than 9 active partitions, the first 9 partitions are
IMPORTANT: For a fire panel that has more than 9 active partitions, the first 9 partitions are
reported to the central station uniquely. Beyond 9 partitions, only the 2nd digit of the partition is
reported along with a leading zero (example partition 14 is reported as 04). The installer must
inform the central station of this condition.
The IPGSM-DPC is compatible with the Honeywell brand FACP’s listed below when the model
659EN Line Fault Monitor is installed.
inform the central station of this condition.
The IPGSM-DPC is compatible with the Honeywell brand FACP’s listed below when the model
659EN Line Fault Monitor is installed.
Honeywell Fire Panel
Communicator
411 family
two
411UD family
two
411UDAC family
two
FireWarden-100-2C family
three
FireWarden-100-2C-FR family
three
FireWarden-50C family
two
FireWarden-50C-FR family
two
MS-10UD-7C family
three
MS-10UD-7C-FR
family one (requires UDACT)
MS-25C family
four
MS-5UD-7C family
three
MS-5UD-7C-FR
family one (requires UDACT)
MS-9050UDC family
two
MS-9050UDC-FR family
two
MS-9200UDLSC family
three
MS-9200UDLSC-FR family
three
MS-9600LSC
family three
Use the DACT-UD2 product to
interface the IPGSM-DPC.
Use the DACT-UD2 product to
interface the IPGSM-DPC.
Honeywell Fire Panel
Communicator
MS-9600LSC-FR family
three
Use the DACT-UD2 product to
interface the IPGSM-DPC.
interface the IPGSM-DPC.
NFS2-3030
family one (requires UDACT)
NFS2-3030-FR
family one (requires UDACT)
NFS2-640
family one (requires UDACT)
NFS2-640-FR
family one (requires UDACT)
NFS-320
family one (requires UDACT)
NFS-320C
family one (requires UDACT)
NFS-320C-FR
family one (requires UDACT)
NFS-320SYS
family one (requires UDACT)
NFS-320SYS-FR
family one (requires UDACT)
NSP-25C family
four
SFP-10UDC family
three
SFP-10UDC-FR family
three
SFP-5UDC family
three
SFP-5UDC-FR family
three