Klaxon 105 DC Manual Do Utilizador

Página de 4
Installation Manual
Installation
a. The sounder is installed by first mounting the base unit and making the
external wring connections to the base. The head unit then automatically
connects when it is attached to the base.
b. The sounder head is separated from the base by unlocking the four
¼-turn fasteners in the corners of the sounder.
(Recommended screwdriver: Philips No. 2, min 100mm long).
c. Note that the head only fits onto the base one way around. If a beacon
is fitted, care should be taken when mounting the base to ensure that
the beacon will be positioned in the desired orientation after the
sounder is attached
Wiring
The sounder and beacon have separate wiring terminals. Each terminal is
duplicated to enable simple ‘daisy-chain’ connection of multiple units.
Controls
a. Tone Selection
The first and second stage alarm tones are independently set using
6-way dipswitches S1 and S2 respectively. The required settings are
shown in the table overleaf. The third stage alarm tone is pre-set to
complement the selected first stage tone as shown in the table.
b. Volume Control
The sound output of the unit can be reduced by up to 20dBA by
adjusting the potentiometer.
c. Beacon Flash Controls (If fitted)
The flash mode of the beacon can be altered using the 2-way
dipswitch marked
EN
Sounder Positive Supply (10 to 60V DC)
Sounder Negative Supply (0V)
2nd Stage Alarm Control (Connect to 0V to activate)
3rd Stage Alarm Control (Connect to 0V to activate)
Beacon Positive Supply (10 to 60V DC)
Beacon Negative Supply (0V)
Line
Terminal Marking
+
-
S2
S3
+
-
XENON BEACON
LED BEACON
Technical Specification:
Supply Voltage Range
10-60V DC
Current – Sounder
8-40mA* (Typ. 30mA @ 24V, Tone 1)
Current –Beacon
Xenon - 250mA Average, 700mA Peak*,
(Where fitted)
LED - 18mA (Flashing) or 65mA (Static)*
Peak Sound Level
100-113 dBA at 1m*
(Typ. 105dBA @ 24V, Tone 1)
Number of Tones
64
Volume Control
20dBA typical
Remote Tone Switching
Provision for 3 alarm stages
(Negative voltage activation)
Operating Temperature
-25°C to +70°C
Casing
High Impact Polycarbonate/ABS
IP Rating
IP66
Synchronisation
Automatic with Klaxon Nexus and
Sonos Sounders
*depends on selected tone and input voltage. See tone table for details.
EN54-3 certified on tones 1,2,3,6,7 & 13 & > 17V DC only.
The European directive “Waste Electrical and Electronic Equipment” (WEEE)
aims to minimise the impact of electrical and electronic equipment waste on
the environment and human health. To conform with this directive, electrical
equipment marked with this symbol must not be disposed of in European public
disposal systems. European users of electrical equipment must now return
end-of-life equipment for disposal. Further information can be found on the
following website: http://www.recyclethis.info/.
From Controller
1st Stage
2nd Stage
3rd Stage
Sounder
Beacon
+
-
+
-
1st Unit
2nd Unit
To Next Unit
Nexus 105 DC Sounder & Sounder-Beacon
Installation Instructions
Switch
Off
On
Off
On
1
60 flashes per min 30 flashes per min Single Flash Double Flash
2
Single Flash
Double Flash
Flashing
Static