Honeywell SMV 3000 Manual Do Utilizador

Página de 217
SMV 3000 Transmitter User’s Manual
1/99
66
6.8
TempConf Configuration  - PV3,  
Continued
ATTENTION
 
For a reverse range, enter the upper range value as the LRV and the
lower range value as the URV. For example, to make a 0 to 500 °F
range a reverse range, enter 500 as the LRV and 0 as the URV.
 
The URV changes automatically to compensate for any changes in the
LRV and maintain the present span (URV – LRV). See Figure 23 for
an example.
 
If you must change both the LRV and URV, always change the LRV
first. However, if the change in the LRV would cause the URV to
exceed the URL, you would have to change the URV to narrow the
span before you could change the LRV
Figure 23
Example of LRV and URV Interaction
Current Range Settings
LRL
      LRV
          SPAN
URV
  URL
-328
      -100
             257
 600
   842  oF
Range Settings After LRV is Changed to Zero (0)
LRL
              LRV
 SPAN
      URV  URL
-328
      -100    0
             257
600  700   842  oF