Univex 318258-000 Manual Do Utilizador

Página de 20
10
Water Heater Location
Centrally located with the water piping system.
 
The fl ooring beneath the water heater must be able to 
 
support the weight of the water heater when fi lled with 
water (967 lbs. full).
Located indoors (such as a basement or garage) 
 
and in a vertical position. Sheltered from freezing 
temperatures.
Provisions made to shelter the area from water    
 
damage. Metal drain pan installed and piped to an 
adequate drain.
Sufficient room to service the water heater.
 
Sufficient air for the heat pump to function. 
 
The water 
heater must be located in a space 750 cubic feet or 
larger, and must have unrestricted airfl ow.  As an 
example, a room that has an 8 foot tall ceiling and is 
10 feet long by 9-1/2 feet wide would contain 760 cubic 
feet. 
 
NOTE:
 For optimal effi ciency and serviceability, the 
following clearances should be maintained: 3 feet on 
the air inlet side, 5 feet on the air outlet side, 6 inches in 
the back, and 2 feet in the front.
 
The unit cannot be placed into any type of closet or 
 
small enclosure.
The site location must be free from any corrosive 
 
elements in the atmosphere such as sulfur, fl uorine, 
and chlorine. These elements are found in aerosol 
sprays, detergents, bleaches, cleaning solvents, air 
fresheners, paint, and varnish removers, refrigerants, 
and many other commercial and household products. 
In addition excessive dust and lint may affect the 
operation of the unit and require more frequent 
cleaning (See “Cleaning the Heat Pump” section).
Ambient air temperature must be above 45°F and 
 
below 109°F. If the ambient air temperature falls 
outside these upper and lower limits the electrical 
elements will activate to meet the hot water demand.
Water System Piping
Temperature and pressure relief valve properly    
 
installed with a discharge pipe run to an adequate drain  
and sheltered from freezing (See Figure 5).
All piping properly installed and free of leaks.
 
Heater completely filled with water (See “Water Piping 
 
System” section).
Closed system pressure buildup precautions installed 
 
(See “Closed System/Thermal Expansion” section).
Mixing valve (when applicable) installed per 
 
manufacturer’s instructions (See “Water Temperature 
Regulation” section).
INSTALLATION CHECKLIST
Condensate Drain Line Installation
Must be located with access to an adequate drain or 
 
condensate pump.
Condensate drain lines installed and piped to an 
 
adequate drain or condensate pump (See Figure 4).
Electrical Connections
The water heater requires 240 VAC for proper 
 
operation.
Wiring size and connections comply with all applicable  
 
codes or in the absence of local or state codes follow 
NFPA-70, the National Electrical Code-current edition.
Water heater and electrical supply are properly    
 
grounded.
Wiring enclosed in approved conduit (if required by 
 
local codes).
Proper overload fuse or circuit breaker protection 
 
installed.
Post Installation Review
Understand how to use the User Interface Module to 
 
set the various modes and functions (See “Adjusting 
the User Interface Module/Operating Modes” section). 
Hybrid Mode is the recommended Operating Mode. 
 
Understand the various Operating Modes and which 
mode may be best based on season, ambient 
temperature, and usage (See “Operating Mode 
Description” section). 
NOTE:
 It may be necessary to temporarily change 
modes if for example filling a spa or hot tub.
Understand the importance of routine inspection/
 
maintenance of the condensate drain pan and lines 
(See “
Inspection/Cleaning of the Condensate Drain 
Pan & Condensate Drain Lines” section)
.  This is to 
help prevent any possible drain line blockage resulting 
in the condensate drain pan overflowing. 
IMPORTANT:
 Water coming from the plastic shroud is 
an indicator that both condensation drain lines may be 
blocked. Immediate action is required.
To maintain optimal operation check, remove and clean 
 
the air filter (See “Air Filter Cleaning/Replacement” 
section).
The Installation Instructions and Use & Care Guide 
 
should be kept with the water heater for reference.