PUMP RECOMMENDATION FOR 
POWER-FIN 0502-1302 WATER HEATER 
 
Pump Specifications 
Part No. 
HorsePower 
Flanges 
Valute Material 
Flange Material 
Vendor 
Vendor Product Series 
Orientation 
PUM3013 2/5  2"  Brass 
Brass  Armstrong E 
Series 
Horizontal 
 
Installation Specifications 
  
Recommended for 
Based on 
      Pump 
Model Numbers 
Maximum GPM 
Installation Type 
  
Power-fin, PF(N,L) 0502-1302 
75 GPM 
Single Water Heater piped to Single Storage Tank 
PUM3013 
Based on 
Based on 
  
  
Minimum Pipe Diameter 
Connecting piping 
  
  
2-1/2" 
Maximum 45 feet straight pipe with 6-Elbows, 2-Unions,2-Ball Valves and 1-Cold Water Inlet Tee  
 
IMPORTANT: Read the Power-fin 0502-2001 Installation and Operation Manual.  If the planned system exceeds 
the pump capacity in flow and/or head see “Pump Curves-All Pumps” for alternate pumps and pump curves.
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 