Honeywell T8570 Manual Do Utilizador

Página de 12
40007507-001 
T6570, T8570 SERIES DIGITAL FAN-COIL THERMOSTATS 
Mounting 
Any T6570, T8570 series thermostat can be mounted directly 
on the wall on a 65x65mm junction box, or a 2"x4" horizontal 
junction box. An optional adapter plate is available for 
mounting on a 4"x4" or vertical junction box. (See Fig. 2) 
Mounting screws are supplied for alternatives. 
1.   Feed leadwires through wiring access hole of wallplate 
and adaptor plate (if used). 
2.   Attach supply wires using wire nuts (not provided), or 
screw terminals, as appropriate. 
3.   Locate wallplate in the horizontal mounting position. See 
Fig. 2 if using the vertical junction box adapter plate. 
4.   Push leadwires into electrical junction box and attach 
wallplate to box using machine screws provided in the 
appropriate mounting holes. 
5.   Attach thermostat to wallplate: 
a.   Locate the two center side holes on the back of the 
thermostat. 
b.   Align the holes with the two wallplate side tabs. 
c.   Press down firmly to snap thermostat into place. 
M17505 
Fig. 2. Mounting the vertical junction box adapter plate 
M17505 Optional adapter plate. 
Removing the thermostat 
CAUTION 
Equipment Damage Hazard.
Improper removal can damage the thermostat. 
Carefully follow the thermostat removal directions. 
If it is necessary to remove the thermostat from the wallplate 
(see Fig. 3): 
1.   Use a screwdriver to pry thermostat left side away from 
the base. 
2.   Use the screwdriver to pry thermostat's right side away 
from the wallplate. 
3.   Use both hands to pull the thermostat straight away from 
the wallplate. 
1
2 
3 
M15396 
Fig. 3. Removing the thermostat 
Thoroughly check wiring to the wallplate before finally 
mounting the thermostat on the wall. 
OPERATION 
Control 
PROPORTIONAL + INTEGRAL (P+I) CONTROL 
Like a mechanical thermostat, the T6570, T8570 Series have 
On/Off control output. However, this output is regulated by a 
P+I algorithm, enabling the thermostat to control closer to 
setpoint than conventional thermostats. This results in 
performance where the space temperature is maintained within 
0.75°C (1.5°F) of the setpoint regardless of fan speed. 
P+I action minimizes the difference between the temperature 
setpoint and the effective control point by adjusting the output 
on-time until the control point matches the setpoint. The on-
time is based on a fixed cycle rate of 4 cycles/hour for cooling 
(8 cycles/hour for heating), and the proportional band is 1.6°C 
(2.9°F). 
NOTE:   Integral action corrects the temperature control errors 
of proportional-only control, but it is slower to react to 
large temperature or setpoint changes. 
These thermostats also feature optional built-in time 
delays for equipment protection which can inhibit 
rapid response to large setpoint changes if active. 
SINGLE-STAGE COOLING OR HEATING CONTROL (SEE FIG. 4) 
In cooling mode the user setpoint will be positioned at the 
bottom of the Proportional Band, so the setpoint will effectively 
be the temperature where the cooling switches off. In heating 
mode the user setpoint will be positioned at the top of the 
Proportional Band, and this will be the temperature where the 
heating switches off. 
NOTE:   This also applies to models with manual heat/cool 
changeover. 
95C-10897–6