Honeywell L91D Manual Do Utilizador

Página de 12
L91A,B,D PROPORTIONING PRESSURETROL
®
 CONTROLLERS
5
60-2152—08
INSTALLATION
When Installing This Product...
1. Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the 
product to make sure the product is suitable for your 
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product opera-
tion as provided in these instructions.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property damage.
1. Disconnect power supply before beginning 
installation to prevent electrical shock and 
equipment damage.
2. When using the controller with a compressor, install 
a dampening device (such as a needle valve, 
header, or surge tank) to dampen pulsations that can 
damage the controller or reduce its life.
IMPORTANT
1. Locate the controller where the ambient temperature 
will not exceed 150° F (66° C).
2. When the controller is used on a boiler, be sure to 
connect a steam trap (siphon loop) between the 
controller and the boiler.
3. Before installing controller, be sure the siphon loop 
has enough water in it to fill lower trap.
4. Use pipe compound sparingly to avoid clogging the 
hole in the pipe or bellows fitting.
5. Do not tighten the controller by hand by holding onto 
the case and turning it.
Location and Mounting
When used with steam boilers, always mount the controller 
above the water line in the boiler. A steam trap (siphon loop) 
must always be connected between the controller and the 
boiler (Fig. 2) to prevent boiler scale and corrosive vapors from 
attacking the bellows. Before installing controller, be sure the 
siphon loop has enough water in it to fill lower trap.
The controller can be mounted (1) beside the pressure gauge, 
(2) in a fitting on the boiler provided by the manufacturer, or (3) 
at a remote location in case of excessive vibration.
Make all pipe connections in accordance with approved 
standards. Use only a small amount of pipe compound to seal 
the connection joints. Excess pipe compound may clog the 
small hole in the fitting and prevent the controller from 
operating properly.
To avoid leaks and damage to the case, use a parallel jaw 
wrench on the controller fitting. Do not tighten the controller by 
hand by holding onto the case and turning it.
Fig. 2. Approximate dimensions in in. (mm) for mounting 
L91 Pressuretrol
®
 Controller beside Pressure Gauge on 
Steam Trap (Siphon Loop).
Mounting Beside a Pressure Gauge
To mount the controller beside a pressure gauge (Fig. 2), 
remove the gauge. In its place, install a steam trap (siphon 
loop) with a tee on top. Using elbows and pipe nipples, mount 
the controller and pressure gauge on the ends of the tee.
Mounting on a Boiler
If it is not convenient to mount the controller beside the 
pressure gauge, install a steam trap (siphon loop) in the fitting 
provided by the boiler manufacturer. If there is no fitting, mount 
the steam trap at a location recommended by the boiler 
manufacturer. Screw the controller directly to the steam trap, if 
possible.
Mounting at a Remote Location
If there is excessive vibration at the boiler that may adversely 
affect the operation of the controller, mount the controller at a 
remote location. All piping from the boiler must be suitable and 
solidly mounted. The piping must be properly pitched to drain 
all condensation back to the boiler. If this causes the controller 
to be located at an inconvenient height (on large boilers), it 
may be mounted at a lower level if the connecting piping is 
filled with clean water. A steam trap (siphon loop) must be 
mounted between the remote piping and the controller.
PRESSURETOL
4-1/2 (114) TO 
5-1/2 (140)
BOILER
STEAM TRAP
(SIPHON LOOP)
TEE
PRESSURE
GAUGE
L91
PRESSURETROL
CONTROLLER
M23884
2
1
1
2
50024585-001 STEAM TRAP IS A 1/4 IN. BRASS PIPE WITH
1/4 - 18 NPT EXTERNAL TRHEADS ON BOTH ENDS.
FITTING ON BELLOWS HAS 1/4-18 NPT EXTERNAL THREADS 
ON 0 TO 16 OZ/SQ. IN. AND 0 TO 15 PSI  MODELS; INTERNAL 
THREADS ON ALL OTHER MODELS. SOME MODELS ARE 
ALSO AVAILABLE WITH 1/4-19 BSP-TR INTERNAL THREADS; 
SEE TABLE 1.