American International PR 130-34 2NV or 2PV Manual Do Utilizador

Página de 32
18
Temperature and Pressure 
Relief Valve
For protection against excessive pressures and tempera-
tures, a temperature and pressure relief valve must be 
installed in the opening marked “T & P RELIEF VALVE”.  
This valve must be design certified by a nationally recog-
nized testing laboratory that maintains periodic inspection 
of the production of listed equipment or materials as meet-
ing the requirements for Relief Valves and Automatic Shut-
off Devices for Hot Water Supply Systems, ANSI Z21.22. 
The function of the temperature and pressure relief valve is 
to discharge water in large quantities in the event of exces-
sive temperature or pressure developing in the water heat-
er. The valve’s relief pressure must not exceed the working 
pressure of the water heater as stated on the data plate.
Important:  Only a new temperature and pressure relief 
valve should be used with this water heater. Do not use 
an old or existing valve as it may be damaged or not ade-
quate for the working pressure of the new water heater. Do 
not place any valve or piping between the relief valve and 
the tank.
The Temperature & Pressure Relief Valve:   
•  Must not be in contact with any electrical part.
•  Must be connected to an adequate discharge line.
•  Must not be rated higher than  the working pressure  
shown on the data plate of the water heater.
•  The BTUH rating of the T & P valve must be  greater 
than, or equal to, the input rating of the water heater
The Discharge Line:
•  Must not be smaller than the pipe size of the relief 
valve or have any reducing coupling installed in the 
discharge line.
•  Must not be capped, blocked, plugged or contain any 
valve between the relief valve and the end of the dis-
charge line.
•  Must terminate a maximum of 6 inches above a floor 
drain or external to the building.
•  Must be capable of withstanding 250°F (121°C) without 
distortion.
•  Must be installed to allow complete drainage of both 
the valve and discharge line.
Explosion Hazard
If the temperature and pressure relief valve 
is dripping or leaking, have a qualified 
service technician replace it.
 
• Do not plug valve.
 
• Do not remove valve.
Failure to follow these instructions can 
result in death or explosion.
Figure 18: Polaris with Auxillary Storage Tank - One or Two 
Temperature System (With or Without Building Recirculation)
Notes on Figure 18:
If tank temperature is set above 
120°F and water is supplied for 
domestic use (hand washing, show-
ering, etc.) a tempering valve must 
be installed in the hot water line to 
domestic fixtures.
Installation must conform to local 
code requirements. If a check valve 
is installed in the cold water sup-
ply line, an expansion tank must be 
installed between the check valve 
and the water heater’s cold water 
inlet.  Set storage tank temperature 
five degrees lower than the water 
heater’s temperature setting.  Using 
the plug cock in the recirculating 
line, adjust the flow in the recirculat-
ing line to five gallons per minute.
*100 Gallon Model Shown.