Application – Three-Phase Motors
Three-Phase Motor Lead Identifi cation
Each motor lead is numbered with two markers, one near each end. To reverse rotation, interchange any two line connections.
L1
T1
U1
T1
U1
T6
W2
T6
W2
L2
T2
V1
T2
V1
T4
U2
T4
U2
L3
T3
W1
T3
W1
T5
V2
T5
V2
L1
L2
L3
Connections for across-the-line starting, 
running, and any reduced voltage starting 
except WYE-DELTA type starters.
WYE-DELTA starters connect the motor as 
shown below during starting, then change to 
the running connection shown at the left.
There are a number of different types of phase converters 
available. Each generates three-phase power from a 
single-phase power line.
In all phase converters, the voltage balance is critical to 
current balance. Although some phase converters may 
be well balanced at one point on the system-operating 
curve, submersible pumping systems often operate 
at differing points on the curve as water levels and 
operating pressures fl uctuate. Other converters may be 
well balanced at varying loads, but their output may vary 
widely with fl uctuations in the input voltage.
The following guidelines have been established for   
submersible installations to be warrantable when used 
with a phase converter.
1.  Limit pump loading to rated horsepower. Do not load 
into motor service factor.
2.  Maintain at least 3 ft/s fl ow past the motor. Use a fl ow 
sleeve when necessary.
3.  Use time delay fuses or circuit breakers in pump 
panel. Standard fuses or circuit breakers do not 
provide secondary motor protection.
4.  SubMonitor may be used with electro mechanical 
type phase converters, however special connections 
are required. Consult SubMonitor Manual for    
connections of receiver and lightning arrestor.
5.   SubMonitor will not work with electronic solid state 
phase converters.
6.  Current unbalance must not exceed 10%.
T5-V2
(YELLOW)
T2-V1
(YELLOW)
T4-U2
(BLACK)
T1-U1
(BLACK)
T6-W2
(RED)
T3-W1
(RED)
LEADS LOCATED HERE ONLY
FOR 3 LEAD (DOL) MOTORS
CHECK VALVE OR 
PIPE PLUG ON RIGHT
SIDE FACING MOTOR
SHAFT
WARNING: When installing 
6-lead motors extra care 
must be used to ensure lead 
identifi cation at the surface. 
Leads must be marked and 
connected per diagram. Motor 
leads are not connected red to 
red, yellow to yellow, etc.
Line Connections — Six-Lead Motors
90° Lead Spacing
Phase Converters