Honeywell P520 Manual Do Utilizador

Página de 16
P520 SIGNAL PROCESSOR
66-2066—01
8
change the displayed value. Once the desired value is 
displayed, press the STORE button. When the set point is 
stored, four dashes are displayed momentarily, indicating that 
the new value was stored into the EEPROM. Illogical settings 
are not accepted; A display of four “E’s” when the STORE 
button is pushed indicates that an error was made when 
selecting the set points. For instance, selecting a flame out set 
point that is equal to or greater than the flame on set point will 
result in this error indication.
The set points can also be selected remotely through the 
serial communication port using a host computer.
Additional Set Points
Table 3. Additional Set Points.
Only adjustment information pertinent to the attached viewing 
head(s) will be visible to the user; for a UV only viewing head, 
no IR GAIN or IR FILTER settings would be shown and for an 
IR only viewing head, no UV GAIN setting would be shown.
To change or adjust any of the 3 additional setpoints shown in 
Table 3, refer to the programming flowcharts towards the back 
of this manual. IR gain adjustments are covered in the next 
section as well.
IR Gain Adjustment
The adjustable range for IR Gain is 0-699 with a factory 
default value of 450. When adjusting IR gain, the user will 
notice gain “jumps”. As the gain is increased, the user will 
notice the following:
a. 000 – 099 is linear and then it jumps to 150
b. 150 - 199 is linear and then it jumps to 250
c. 250 - 299 is liner and then it jumps to 350
d. 350 - 399 is linear and then it jumps to 450
e. 450 - 499 is liner and then it jumps to 550
f. 550 - 599 is linear and then it jumps to 650
g. 650 - 699 is linear
With each step change or “jump”, the gain is double but values 
in between are liner. For example, a setting of 250 doubles the 
gain setting of 150. When gain is adjusted to 000, the IR 
contribution is zero. 
There are 8 high pass filter settings available for most IR 
viewing heads (model dependent) as shown below.
1 = 16 HZ
2 = 24 HZ
3 = 33 HZ
4 = 52 HZ
5 = 75 HZ
6 = 100 HZ
7 = 155 HZ
8 = 215 HZ 
Flame Failure Response Time (FFRT)
The flame failure response time, or F.F.R.T., is defined as the 
time it takes for the flame relay to de-energize after the flame 
signal (from the viewing head) is below the programmed 
Flame Off setpoint. This time delay is programmable from 
both the front panel of the P520 and a remote, host computer. 
Only three settings are possible: one, two and three seconds.
The maximum time delay is limited to three seconds in 
compliance with the FM (Factory Mutual) limit of the F.F.R.T. to 
be less than four seconds.
4-20mA Remote Output
The standard remote meter output has a 0-20mA range and is 
designed to drive remote meters, as explained earlier in this 
manual. You can convert this output to a 4-20mA range, as 
follows:
Press the front panel push-buttons (indicated in Table 4) whil
holding down both the up arrow and down arrow buttons. 
Press all buttons in each row together (i.e., three in the first 
row, two in the second row, and three in the last row).
Doing this toggles the function back and forth between the 0-
20mA and 4-20mA ranges.
The change will be verified by four dashes “----” and “4-20” 
momentarily displayed. If the signal processor is programmed 
for the 4-20mA range, “4-20” will be displayed; toggling back 
to the 0-20mA range will again cause four dashes to appear 
on power-up of the unit. The factory default setting is 4-20.
The 4-20mA signal from the P520 is powered from the P520 
itself. When sending the signal to a remote device (such as a 
distributed control system, PLC or burner management 
system), the input must be isolated. If there is a ground 
potential difference between the two systems, then there 
could be noise and performance problems. When using a 
remote meter by itself, this will not occur, because it will not be 
tied into another electrical system (will not be sharing 
grounds).
The bargraph reading on the front panel will not be affected by 
this change to 4-20mA output. It will remain the same as 
before (i.e., show zero on no signal detected). The 4-20mA 
output will still perform the same way on the high end (i.e., on 
a strong signal, it will saturate at the same level, slightly above 
22mA).
Specifications for the analog current output signal are 
provided in the SPECIFICATIONS section.
Set Point
Display
Number
IR GAIN
3 DIGIT NUMBER
0-699
IR FILTER
1 DIGIT NUMBER
1-8
UV GAIN
2 DIGIT NUMBER
0-99
Table 4. Remote Output Setting.
FLAME 
ON
FLAME 
OFF
GAIN 
SET
F.F.R.T.
TIME DELAY
 ON
X
X
X
X
X
X
X
X