3 -  28 
3. SIGNALS AND WIRING 
 
3.7.3 Power-on sequence 
(1) Power-on procedure 
1) Always wire the power supply as shown in above section 3.7.1 using the magnetic contactor with 
the main circuit power supply (three-phase 200V: L
1
, L
2
, L
3
, single-phase 230V  single-phase 
100V: L
1
, L
2
). Configure up an external sequence to switch off the magnetic contactor as soon as an 
alarm occurs. 
2) Switch on the control circuit power supply L
11
, L
21
 simultaneously with the main circuit power 
supply or before switching on the main circuit power supply. If the main circuit power supply is not 
on, the display shows the corresponding warning. However, by switching on the main circuit power 
supply, the warning disappears and the servo amplifier will operate properly. 
3) The servo amplifier can accept the servo-on (SON) about 1 to 2s after the main circuit power supply 
is switched on. Therefore, when servo-on (SON) is switched on simultaneously with the main circuit 
power supply, the base circuit will switch on in about 1 to 2s, and the ready (RD) will switch on in 
further about 20ms, making the servo amplifier ready to operate. (Refer to paragraph (2) of this 
section.) 
4) When the reset (RES) is switched on, the base circuit is shut off and the servo motor shaft coasts. 
 
(2) Timing chart 
20ms
20ms
20ms
10ms
10ms
10ms
10ms
10ms
60ms
60ms
SON accepted
(1 to 2s)
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Power supply
Base circuit
Servo-on
(SON)
Reset
(RES)
Ready
(RD)
 
(3) Forced stop 
 
 CAUTION 
Provide an external forced stop circuit to ensure that operation can be stopped and 
power switched off immediately. 
 
Forced stop (EMG) can be used by making device setting on the MR Configurator (servo configuration 
software). 
Make up a circuit which shuts off main circuit power as soon as EMG-SG are opened at a forced stop. 
To ensure safety, always install an external forced stop switch across EMG-SG. By disconnecting 
EMG-SG, the dynamic brake is operated to bring the servo motor to a sudden stop. At this time, the 
display shows the servo forced stop warning (AL.E6). 
During ordinary operation, do not use the external forced stop (EMG) to alternate stop and run. 
The servo amplifier life may be shortened. 
Servo amplifier
EMG
SG
VDD
COM
Forced stop