DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Additional Maintenance Procedures 
6-39
Removing and Restoring Power 
6
The three test types should have extension numbers assigned on the 
Maintenance-Related System Parameters Form.
Test Type 100:___   Test Type 102:___   Test Type 105:___
Test Type 100 provides:
5.5 seconds of 1004 Hz tone at 0dB
Quiet until disconnect; disconnect is forced after one minute
Test Type 102 provides:
9 seconds of 1004 Hz tone at 0dB
1 second of quiet
This cycle is repeated until disconnect; disconnect is forced after 24 
hours.
Test Type 105 provides:
9 seconds of 1004 Hz at -16dB
1 second of quiet
9 seconds of 404 Hz at -16dB
1 second of quiet
9 seconds of 2804 Hz at -16dB
30 seconds of quiet
1/2 second of Test Progress Tone (2225 Hz)
Approximately five seconds of quiet
Forced disconnect
Removing and Restoring Power
!
CAUTION:
Error Log information is lost when the PPN cabinet is powered down. If this 
information is to be saved, enter the reset system 4 command. The 
command will take several minutes to complete, and will result in saving of 
the Error Log to the MSS.
!
CAUTION:
Before powering down a cabinet or carrier that contains DEFINITY AUDIX 
circuit packs (TN566 and TN2169), you must first power down the AUDIX 
unit to avoid damage to the AUDIX software Instructions for powering down 
this unit appear on the circuit pack and in DEFINITY AUDIX documentation.