DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets  
555-230-112  
Issue 5
May 1998
Install and Connect Cabinets 
Page 1-9
Connect AC Power and Ground 
1
NOTE:
If the EPN cabinet is located remote from the PPN cabinet (in a 
separate room or building), connect the CABINET GROUND wire to 
an approved ground.
Figure 1-1.
Typical Cabinet Ground Location
5. Repeat connecting each EPN cabinet to the single-point ground block.
Figure Notes
1. PPN Cabinet
2. EPN Cabinet (if Installed)
3. 6 AWG (#40) (16 mm
2
) CABINET GROUND 
Wire
4. Cabinet Ground Terminal Block
5. AC Load Center 
Single-Point Ground
6. Less than 50 Wire Feet 
(15.2 m)
7. 10 AWG (#25) (6 mm
2
Ground Wire to CBC
widmgrnd LJK 092697