Roberts Gorden 45 Manual Do Utilizador

Página de 62
UHA L
OW
 P
ROFILE
 U
NIT
 H
EATER
 I
NSTALLATION
 O
PERATION
 
AND
 S
ERVICE
 M
ANUAL
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Basic Information
UHA[X][S] heaters have automatic ignition burners 
for ON/OFF operation only. 
3.2 Manufactured Units
Gas-fired, power-vented unit heater with tubular heat 
exchanger. Units shall have a minimum of 82% 
thermal efficiency. The standard unit shall consist of 
a non-separated combustion design with an 
aluminized heat exchanger. Design and heat 
exchanger alternatives shall be offered as follows:
• Separated Combustion: A separated combustion 
unit shall consist of an enclosed sealed burner 
box to which combustion air is vented through a 
piece of internal flexible air duct. This duct 
terminates at an exterior cabinet flange to which 
a vent ran to the outside of the heated space 
should be attached.
• Stainless Steel Heat Exchanger: A stainless 
steel heat exchanger unit shall consist of heat 
exchanger tubes, heat exchanger tube supports, 
heat exchanger tube plates and a vent box 
produced of 409 stainless steel.
3.3 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed in a level position with 
horizontal discharge.
• May be mounted on a shelf of non-combustible 
material using shelf mounting brackets.(See 
Page 11, Figure 6
 and Page 12, Figure 7 for 
details.)
• May be suspended from above (See Page 11, 
Figure 5) or from wall brackets of sufficient 
strength to support the heater as listed in the 
Dimension Data Table on Page 49, Section 15.1
Drop rods must be a minimum of 3/8" diameter 
mild steel. Four suspension points (3/8" nuts) 
are located on top of the heater. 
• Must be installed in a manner which allows 
access to all serviceable components.
See Page 7, Figure 4 for details.
3.4 Minimum Required Installation Clearances
Clearances around the heater and vent must be as 
indicated on Page 7, Figure 4Page 17, Figure 9 
through Page 20, Figure 14 to ensure access for 
servicing, and correct operation.
3.5 Clearances to Combustibles
Clearances must be as indicated on Page 7, Figure 
4
. If clearances to combustibles are not indicated, 
then installation clearances apply.
3.6 Ventilation
It is important to ensure that there is adequate air 
space around the heater to supply air for 
combustion, ventilation and distribution in 
accordance with local and national code on Page 
14, Section 6
.
WARNING
Fire Hazard
Some objects can catch fire or explode 
when placed close to heater.
Keep all flammable objects, liquids and 
vapors the required clearances to 
combustibles away from heater.
Failure to follow these instructions can 
result in death, injury or property damage.
WARNING
Carbon Monoxide Hazard
Heaters may be installed 
vented or unvented.
Vented heaters must be 
vented outdoors.
Unvented heaters must be 
installed in buildings with 
ventilation rates as per 
section 6.4.
Failure to follow these 
instructions can result in 
death or injury.