Roberts Gorden CTCU 22 Manual Do Utilizador

Página de 40
SECTION 3: C
RITICAL
 C
ONSIDERATIONS
3
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Basic Information
CTCU heaters have automatic ignition burners for 
ON/OFF operation only. 
3.2 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed in a level position with horizon-
tal or vertical discharge.
• May be mounted on a shelf of non-combustible 
material. (See Page 5, Section 4 and Page 7, 
Figure 2
 for support points.)
• May be suspended from above (See Page 7, Fig-
ure 2) or from wall brackets of sufficient strength 
to support the heater as listed in the Dimension 
Data Table on Page 5, Section 4.1. Drop rods 
must be a minimum of 10 mm diameter mild 
steel. Four suspension points (M10 nuts) are 
located on top and back side of the heater. 
• Must be installed in a manner which allows 
access to all serviceable components.
3.3 Minimum Required Installation Clearances
Clearances around the heater and flue must be as 
indicated on Page 4, Figure 1Page 9, Figure 5 
through Page 10, Figure 7 to ensure access for 
servicing, and correct operation.
3.4 Clearances to Combustibles
Clearances must be as indicated on Page 4, Figure 
1
. If clearances to combustibles are not indicated, 
then installation clearances apply.
3.5 Ventilation
It is important to ensure that there is adequate air 
circulation around the heater to supply air for 
combustion, ventilation and distribution in 
accordance with local and national codes.
3.6 Gas Supply
It is important that the gas supply pipe is sized 
correctly to provide the inlet pressure as stated on 
the heater data plate. The gas supply pipe and 
electrical connections must not support any of the 
heater's weight. 
3.7 Electrical Supply
A permanent 230 V 50 Hz 1 Ø electrical supply is 
required at the main electrical terminals. The heater 
also requires suitable energy controls in accordance 
with Section 9.
3.8 Flue 
Choose heater siting to allow for the proper location 
of the flue. Each heater must be fitted with an 
individual and correctly sized sealed flue system 
(See Page 9, Section 6). 
No other appliance may be connected to the flue. 
For room sealed installation, the air intake must be 
the same size sealed system and the flue/air intake 
must terminate at an approved concentric wall or 
roof terminal.