Section 5 Troubleshooting
TP-6843   1/13
5.5 Troubleshooting
Figure 5-2 contains generator set troubleshooting, diagnostic, and repair information.  Check for loose connections 
before replacing parts.
 Figure 5-2
Figure 5-2 General Troubleshooting Chart
Problem
Possible Cause
Recommended Action
Controller 
display backlight 
is off.  
Backlight turns off after about 1 minute with no 
activity.  
Backlight will turn on when a button is pressed or the 
generator set starts.  
Controller 
display is off.  
Low or no battery voltage.  
Check connections.  
Check generator set battery.  See Figure 1-2.  
The generator 
set does not 
crank.  
Battery weak or dead.  
Recharge or replace the battery.  
Battery connections reversed or poor.  
Check the connections.  
Fault shutdown.  
Check the controller display for fault messages.  See 
Section 2.6.  Correct the fault condition and reset the 
controller.  
Generator set in the OFF mode.  
Press the RUN button to start the engine or press AUTO 
to allow remote starting.  
The generator 
set cranks but 
does not start, 
starts hard, 
lacks power, or 
operates 
erratically.  
Air cleaner clogged.  
Clean and/or replace the air cleaner.  
Battery weak or dead.  
Recharge or replace the battery.  
Battery connection poor.  
Clean and tighten the battery connections.  
Spark plug wire connection loose.  
Check the spark plug wires.  
Low oil pressure shutdown.  
Check for oil leaks.  Check the oil level and add oil if 
necessary.  
Fuel pressure insufficient.  
Check the fuel supply and valves.  
Engine malfunction.  
Contact an authorized Kohler distributor/dealer.  
No DC output.   Line circuit breaker in the OFF position.  
Place the circuit breaker in the ON position.  
Line circuit breaker tripping because of overload.   Reduce the load on the generator set.  
Line circuit breaker tripping because of short 
circuit.  
Contact an authorized Kohler distributor/dealer for 
service.  
Rectifier has failed.  
Verify that the generator is providing AC voltage.  
Low output or 
excessive drop 
in voltage.  
Generator set overloaded.  
Reduce the load.  
Generator set 
stops suddenly.  
Low oil pressure shutdown.  
Check for oil leaks.  Check the oil level and add oil if 
necessary.  
Out of fuel.  
Check fuel supply.  
Overcrank shutdown.  
Reset the controller.  If the overcrank fault occurs again, 
contact an authorized Kohler distributor/dealer.  
Auxiliary winding circuit breaker tripped.  
Reset the circuit breaker (located in controller’s service 
access area).  Contact an authorized Kohler 
distributor/dealer for service if breaker trips repeatedly.  
Fault shutdown.  
Check the controller display for fault messages.  See 
Section 2.6.  Correct the fault condition and reset the 
controller.  
Generator set in the OFF mode.  
Press the RUN button to start the engine or press AUTO 
to allow remote starting.  
Remote stop command received from a remote 
switch, or OnCue
®
.  
Check the remote switch position.  Check OnCue
®
.  
Engine malfunction.  
Contact an authorized Kohler distributor/dealer.