PAGE 26 — DCA45SSIU3 50 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (12/19/08) 
GENERATOR OUTPUTS
GENERATOR OUTPUT VOLTAGES 
A wide range of voltages are available to supply voltage for 
many different applications. Voltages are selected by using 
the voltage selector switch (Figure 12). To obtain some of 
the voltages as listed in Table 7 (see below) will require a 
fi ne adjustment using the voltage regulator (VR) control 
knob
 located on the control panel. 
Voltage Selector Switch
The voltage selector switch (Figure 12) is located above 
the output terminal panel’s Hard Wire Hook-up Panel.  It 
has been provided for ease of voltage selection.
Voltage Change-Over Board
Figure 12. 
Voltage Selector Switch Locking Button
The voltage selector switch has a locking button to protect 
the generator and load from being switched while the 
engine is running. To lock the voltage selector switch, press 
and hold  the red button located at the bottom of the switch.
  CAUTION
NEVER change the position of the voltage selector 
switch while the engine is running. ALWAYS place 
circuit breaker in the OFF position before selecting 
voltage.
Voltages Available
Table 7. 
Three Phase 
(Switchable)
200V
220V
416V
440V
Single Phase 
(Switchable)
115V
127V
240V
254V
Maximum Amps
Table 8 shows the maximum amps the generator can 
provide. DO NOT exceed the maximum amps as listed..
Generator Maximum Amps
Table 8. 
Rated Voltage
Maximum Amps
Single Phase 100 Volt
98 amps (4 wire)
Single Phase 200 Volt
48 amps (4 wire)
Three Phase 200 Volt
104 amps
Three Phase 400 Volt
52 amps