Armstrong World Industries A1000CU Manual Do Utilizador

Página de 43
 
AR-EXP-CUMMINS-07-00 
 
OWNERS MANUAL     
Page 43 
In case of complete overhaul  of genset, the bearing of the 
generator should be changed. 
On  request  prelubricated  bearings  with  regreasing  system 
can  be  mounted.  When  regreasing  use  20/  30  grams  of 
grease. 
Following types of grease are to be recommended  for nor-
mal application: 
 
MOBIL OIL: MOBILUX 3 
SHELL: ALVANIA 3 
AGIP: GR MW 3 
ESSO: BEACON 3 
 
10.3.  VOLTAG REGULATOR 
 
The generators are provided with automatic voltage regula-
tor.  The  AVR  is  provided  with  potentiometers  to  adapt  the 
characteristics of the AVR to different operating conditions. 
 
The  AVR  is  provided  with  adjustable  stability  circuitry  to 
allow operations in a wide range of applications.  
 
The  AVR  is  equipped  also  with  protecting    circuit  allowing 
the generator to operate underspeed if not loaded. 
 
 ATTENTIONI: it is not advisable to have the generator oper-
ating loaded when the frequency (speed) is below the rated 
value:  this  kind  of  operation  is  an  overload  for  the  whole 
generator excitation system. 
 
CONNECTION OF AVR 
The AVR is connected to the terminals of the generator and 
to exciter FAST-ON terminals. 
 
USE OF POTENTIOMETERS 
P1/VOLT- Potentiometer for adjusting the output voltage of 
the generator; it allows a wide range of voltage setting (i.e. 
between  350  and  470  V;  or  between  170  and  260  V  de-
pending  on  winding  connections)).  When  resetting  the  po-
tentiometer, the voltage has to be set in the range +5%,-5% 
around the rated voltage of the machine. In order to obtain 
a  finer  regulation,  or  to  adjust  the  voltage  from  control 
panel or to limit the voltage range, it is possible to insert an 
external potentiometer. 
 
P2/FREQ- Potentiometer for changing the low speed protec-
tion. Usually it is set in order to reduce the excitation when 
the  speed  is  10  %  below  the  rated  value  at  50  Hz.  By  re-
moving  the  bridge  which  is  normally  shorting  the  auxiliary 
terminals  60-Hz  of  the  regulator,  the  low  speed  protection 
acts properly for 60 Hz. 
 
P3/STAB-  Potentiometer  for  stability  adjust.  By  rotating  it 
clockwise  the  stability  of  the  regulator  increases,  but  the 
response time becomes longer. 
 
P4/AMP- Potentiometer for chancing the overexcitation limit 
device. The overexcitation limit  device  helps to protect the 
excitation system. This device is delayed to avoid transitory 
conditions (in case of overexcitation). 
 
On the AVR there is a protecting fuse. ln case it should be 
necessary to replace it, high speed fuses should be used; in 
addition  they  should  have  high  breaking  resistance  with  a 
rated voltage of 50OV, and rated current of 1OA. The AVR is 
connected to the terminals of the  generator and to  exciter 
using FAST—ON terminals. 
 
 
Phone: (305) 470 0058   
Fax: (305) 470 0068
  
Toll Free: 1-800 238 0732
  
8254 NW 58th St., Miami, FL. 
33166, U.S.A.
  
e-mail:
 
ARMTRONG POWER 
SYSTEMS