Yamaha EF2400iS Manual Do Utilizador

Página de 41
– 7 –
Ground (earth) Lead
Diameter:
0.12 mm (0.005 in)/ampere
EX;
10 Ampere 
→ 1.2 mm (0.05 in)
1
2
1
741-122
AE01181
CONNECTION NOTES
9 Avoid connecting the generator to commercial
power outlet.
1 Correct
2 Incorrect
AE00091
CONNECTION
w
Before the generator can be connected to a build-
ing’s electrical system, a licensed electrician must
install an isolation (transfer) switch in the build-
ing’s main fuse box. The switch is the connection
point for generator power and allows selection of
generator or main line power to the building. This
will prevent the generator from charging the main
power line (backfeeding) when the main power sup-
ply has failed or has been turned off for line repair.
Backfeeding can electrocute or injure line mainte-
nance personnel. Also, generator and building
electrical system damage can occur when normal
operating power returns if unit is used without an
isolation switch.
AE00086
EXTENSION CORD NOTES
9 When using an extension cord, its total length
should not exceed
60 meters for cross section of 1.5 mm square
and
100 meters for cross section of 2.5 mm square.
9 This extension cord should be protected by a tough
flexible rubber sheath (IEC 245) or the equivalent
to withstand mechanical stresses.


 7CF-9-10-a  3/9/05 9:21 AM  Page 7