Siemens 505-2557 Manual Do Utilizador

Página de 68
Advanced Function Programming
3-10
SIMATIC 505–2557 Installation and Operation Guide
Internal Register Structures (continued)
The discrete output points consist of Y17 – Y32.
Y17 – Y19 are used to identify the data being transferred. As data is loaded
to the module, the state of these bits identifies the type of data being
transferred (see Table 3-6). The SIMATIC 505–2557 module decodes these
bits and processes the data accordingly.
Table 3-6
Data Identification Bits
Y19
Y18
Y17
Data Transfer Type
0
0
0
No operation
0
0
1
Function enable bits
0
1
0
Low/High alarm setpoint values
0
1
1
Scaling low/high values
1
0
0
Filtering time constant/Number of
averages
In addition, Y27 – Y32 are used to reset averaging, reset valley hold values,
reset peak hold values, read peak or valley values, read flags, and to write
data to the module. See Figure 3-5.