Unattended Start Protection 
If the Run command is already set when power is turned ON, the inverter starts running 
immediately after powerup. The Unattended Start Protection (USP) function prevents that 
automatic startup, so that the inverter will not run without outside intervention. When USP 
is active and you need to reset an alarm and resume running, either turn the Run 
command OFF, or perform a reset operation by the terminal [RS] input or the keypad 
Stop/reset key. 
In the figure below, the [USP] feature is enabled. When the inverter power turns ON, the 
motor does not start, even though the Run command is already active. Instead, it enters 
the USP trip state, and displays 
E
 
13
 error code. This requires outside intervention to reset 
the alarm by turning OFF the Run command per this example (or applying a reset). Then 
the Run command can turn ON again and start the inverter output. 
 
 
 
 
 
 
 
 
 
Option 
Code 
Terminal 
Symbol 
Function Name 
State
Description 
ON 
On powerup, the inverter will not resume a Run 
command (mostly used in the US) 
13 
USP Unattended 
Start 
Protection 
OFF
On powerup, the inverter will resume a Run 
command that was active before power loss 
Valid for inputs: 
C001
~
C007
 
Required settings  (none) 
Notes: 
•  Note that when a USP error occurs and it is 
canceled by a reset from a [RS] terminal input, the 
inverter restarts running immediately. 
•  Even when the trip state is canceled by turning 
the terminal [RS] ON and OFF after an under 
voltage protection 
E09
 occurs, the USP function 
will be performed. 
•  When the running command is active immediately 
after the power is turned ON, a USP error will 
occur. When this function is used, wait for at least 
three (3) seconds after the powerup to generate a 
Run command. 
Example (default input configuration shown see 
page 66
): 
 
 
 
 
 
 
 
 
See I/O specs on 
page 21,22.
 
 
 
Inverter output frequency
0
t
Inverter power supply 1
0
Alarm output terminal 1
0
[USP] terminal 1
0
Run command [FW,RV] 1
0
Events:
E13
 
Alarm
cleared
Run
command
USP
 
7
6
5
4
3
2
1
 