Xantrex Technology 10 Manual Do Utilizador

Página de 68
Operation
3–6
975-0251-01-01
Idle Sensitivity (Switch #5 and 6)
Most installations will be connected to the 
electrical system. With no appliances turned on, this represents a small load. This 
is due to the capacitance of the wires. Using a trial and error process, the idle 
circuit can be adjusted until the unit will detect small loads but still drop into idle 
mode when all loads are shut off.
Some small loads may not pull the unit out of idle mode. In this case, you may 
disable the idle circuit or use an additional load, such as a small incandescent 
light, to first activate the idle circuitry. You can confirm if the unit is in idle mode 
by checking the DC Amps bar graph, the lowest LED goes out only when the unit 
is in idle mode. 
A volt meter can also be used to confirm the idle condition. Idle mode output 
voltage will typically measure between 10 and 55 volts with an averaging AC volt 
meter. Refer to the Troubleshooting section for a discussion of measuring inverter 
output voltage with a meter.
Power Sharing (Switch #7 and 8)
These switches should be set to match the 
value of the circuit breaker which protects the incoming AC power. For instance, 
in most RV parks or marinas a 15-amp circuit is available. Use the 2-amp setting 
for small generators, or for charging deeply discharged batteries. See page 3–15.
DIP Switch Status
You can check the position of the DIP switches by quickly cycling the power 
switch off and on twice. The DC Volts bar graph will cease to display battery 
voltage and will indicate the setting of each DIP switch. In this mode the bottom 
LED will illuminate if switch 1 is on, etc. DIP switch settings are indicated for 10 
seconds after which time the display returns to indicating battery voltage.
DIP Switch Programming
Table 3-2 DIP switch function and position summary
Feature
Switch Number
Set Point
Equalize or 3-Stage 
Charging
1
Toggle On/Off
Equalize (Do not leave on.)
Off
3-Stage Charging*
**Battery Type
2
3
On
On
Warm Gel Cell (>27 °C)
Off
On
Cool Gel Cell (<27 °C)
On
Off
Warm Wet Cell (>27 °C)
Off
Off
Cool Wet Cell (<27 °C)*
Auto Charge
4
On
Disable: Charger responds to 
On/Off switch.