Lincoln Electric IM604-B Manual Do Utilizador

Página de 38
15
15
RANGER 8 LPG
1. Install a double pole, double throw switch between
the power company meter and the premises
disconnect.
Switch rating must be the same or greater than
the customer’s premises disconnect and service
overcurrent protection.
2. Take necessary steps to assure load is limited to
the capacity of the Ranger 8 by installing a 35 amp
230V double pole circuit breaker.  Maximum rated
load for the 230V auxiliary is 35 amperes. Loading
above 35 amperes will reduce output voltage
below the allowable -10% of rated voltage which
may damage appliances or other motor driven
equipment.
3. Install a 50 amp 115/230V plug (NEMA type 14-50)
to the Double Pole Circuit Breaker using No. 8, 
4 conductor cable of the desired length.  (The
50 amp 115/230V plug is available in the
optional plug kit.)
4. Plug this cable into the 50 amp 115/230V 
receptacle on the Ranger 8 case front.
Figure 1
CONNECTION OF RANGER 8 TO PREMISES WIRING
230 Volt
60 Hz.
3-Wire
Service
POWER
COMPANY
METER
230 VOLT
115 VOLT
115 VOLT
LOAD
N
NEUTRAL
BUS
GROUND
PREMISES
DISCONNECT AND
SERVICE
OVERCURRENT
PROTECTION
GND
N
NOTE:  No. 8 COPPER CONDUCTOR CABLE SEE
NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
SIZE RECOMMENDATIONS.
230 VOLT
GROUNDED CONDUCTOR
35AMP
230 VOLT
DOUBLE
POLE
CIRCUIT
BREAKER
DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
PROTECTION.
50 AMP, 115/230
VOLT PLUG
NEMA TYPE 14-50
50 AMP, 115/230 VOLT
RECEPTACLE
Connection of Ranger 8 to premises wiring must be done by a licensed electrician and must comply with
the National Electrical Code and all other applicable electrical codes.
WARNING