Lynx R FR 5011 Manual Do Utilizador

Página de 39
Reference Manual R FR 5010 Version1.4
 
Page 28   
Rack Installation 
If you have an empty R FR 5010 rack frame we 
recommend you assemble the connection plates 
and modules as well as any options such as the 
redundant power supply and controller before 
mounting the Rack Frame into a 19” inch rack. 
(Please refer to assembly section) 
 
Location 
The R FR 5010 Rack frame can be located 
anywhere there is available 19-inch rack space. 
The rack will take up 2 Rack Units (RU) of vertical 
rack space. 
 
Ventilation 
Depending on the installed modules up to three     
R FR 5010 rack frames can be mounted stacked, 
with no space in-between. Allowance has been 
made in the design providing space between the 
racks for adequate air ventilation. Every third rack 
there should be 1 RU space provided for additional 
airflow. 
NOTE: In case of modules with higher power 
dissipation, e.g. P VD 5010, appropriate cooling is 
required. We recommend in these cases to add 1 
RU space in between each rack. 
The R FR 5011 with a front cover with integrated fans 
should be used for critical applications where 
external cooling is not sufficient. 
 
Note. Airflow through the R FR 5010 rack frame is 
from bottom to top. Forced (fan) cooling may be 
required in case of modules with higher power 
dissipation. Please consider other surrounding 
equipment when designing rack layout. Placing the 
R FR 5010 directly above another piece of 
equipment with heat exhaust from the top may 
cause the Card Modules to malfunction due to 
excessive heat. Like wise, if placed below another 
piece of equipment with bottom air intake the R FR