Status Indicators
Troubleshooting
Voltage Sensitivity Adjustment (optional)
The Back-UPS detects and reacts to line voltage distortions by transferring to battery 
backup power to protect connected equipment. In situations where either the Back-UPS 
or the connected equipment is too sensitive for the input voltage level it is necessary to 
adjust the transfer voltage.
1. Connect the Back-UPS to a wall outlet. The Back-UPS will be in Standby mode, no 
indicators will be illuminated.
2. Press and hold the ON/OFF button for 10 seconds. The OnLine LED will 
illuminate alternately green-amber-red, to indicate that the Back-UPS is in 
Program mode.
3. The Power On/Replace Battery LED will flash either green, amber, or red to 
indicate the current sensitivity level. Refer to the table for an explanation of the 
transfer voltage sensitivity levels.
4. To select LOW sensitivity, press and hold the ON/OFF button until the LED flashes 
green.
5. To select MEDIUM sensitivity, press and hold the ON/OFF button until the LED 
flashes red.
6. To select HIGH sensitivity, press and hold the ON/OFF button until the LED flashes 
amber.
7. To exit Program mode wait five seconds and all LED indicators will extinguish. 
Program mode is no longer active.
Service
If the unit requires service, do not return it to the dealer. Follow these steps:
1. Review the Troubleshooting section of the manual to eliminate common problems.
2. If the problem persists, contact APC Customer Support.
a. Note the model number and serial number and the date of purchase. The model 
and serial numbers are located on the rear panel of the unit and are available 
through the LCD display on select models.
b. Call APC Customer Support and a technician will attempt to solve the problem 
over the phone. If this is not possible, the technician will issue a Returned 
Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free. 
d. Service procedures and returns may vary internationally. Refer to the APC Web 
site for country specific instructions.
3. Pack the unit properly to avoid damage in transit. Never use foam beads for 
packaging. Damage sustained in transit is not covered under warranty. Always 
DISCONNECT THE UPS BATTERY before shipping in compliance with U.S. 
Department of Transportation (DOT) and IATA regulations. 
The battery may 
remain in the unit.
4. Write the RMA# provided by Customer Support on the outside of the package.
5.
Return the unit by insured, pre-paid carrier to the address provided by 
Customer Support.
Contact
APC Web site, www.apc.com
Status
LED Indicator
Audible Indicator On
Audible Indicator Terminates
Power On 
The Back-UPS is supplying utility power to connected equipment.
The green LED illuminates.
None
N/A
On Battery
Back-UPS supplying battery power to battery backup outlets.
The green LED illuminates. The LED 
is not illuminated during the beeps.
Back-UPS beeps 4 
times every 30 seconds.
Beeping stops when utility power is restored or 
the Back-UPS is turned off.
Low Battery warning
The Back-UPS is supplying battery power to the battery backup outlets 
and the battery is near a total discharge state.
The green LED illuminates with rapid 
green flashes.
The Back-UPS emits 
rapid beeping, every 
1/2 second.
Beeping stops when utility power is restored or 
the Back-UPS is turned off.
Replace Battery
• The battery is disconnected.
• The battery needs to be charged, or replaced.
• Replace Battery LED flashes.
• Replace Battery and Power On 
LEDs flash alternately.
Constant tone
Constant tone
Back-UPS is turned off.
Overload Shutdown
While on battery power an overload condition has occurred in one or 
more of the battery backup outlets while the Back-UPS is operating on 
battery power.
None
Constant tone
Back-UPS is turned off.
Sleep Mode
While on battery power the battery is completely discharged. The 
Back-UPS will “awaken” once utility power is restored.
None
The Back-UPS beeps 
once every four 
seconds.
The beeping stops when: 
• Utility power is restored
• If utility power is not restored within 32 seconds
• The Back-UPS is turned off
Building Wiring Fault
The building wiring presents a shock hazard that must be corrected by a 
qualified electrical.
Building Wiring Fault LED 
illuminates red 
None
The Back-UPS is unplugged from the wall outlet 
or is plugged into an improperly wired outlet.
Problem and Possible Cause
Solution
The Back-UPS will not turn on
The Back-UPS has not been turned 
on.
Press the P
OWER
 
ON
 button.
The Back-UPS is not connected to 
utility power, there is no utility power 
available at the wall outlet, or the 
utility power is experiencing a 
brownout or over voltage condition.
Make sure the power cord is securely connected to 
the wall outlet, and that there is utility power 
available at the wall outlet.Where applicable, 
check that the wall outlet is switched on.
The battery is not connected.
Connect the battery. Refer to “Connect the 
Battery” on page 1
 of this manual.
In the event that the Back-UPS receives no utility 
power and the battery is connected, a cold-start can 
be initiated. Press and hold the Power On button 
until the Back-UPS emits two beeps.
The Back-UPS is on, the Replace Battery LED flashes and the unit emits a 
constant tone
The battery is disconnected.
Connected equipment loses power
A Back-UPS overload condition has 
occurred.
Remove all nonessential equipment connected to 
the outlets. One at a time reconnect equipment to 
the Back-UPS.
The Back-UPS battery is completely 
discharged.
Connect the Back-UPS to utility power and allow 
the battery to recharge for eight hours.
PowerChute software has performed a 
shutdown due to a power failure.
This is normal Back-UPS operation.
Connected equipment does not accept 
the step-approximated sine waveform 
from the Back-UPS.
The output waveform is intended for computers 
and peripheral devices. It is not intended for use 
with motor driven equipment.
The Back-UPS may require service.
Contact APC Technical Support for more in depth 
troubleshooting.
The Power On LED is illuminated and the Back-UPS beeps 4 times every 30 
seconds
The Back-UPS is operating on battery 
power.
The Back-UPS is operating normally on battery 
power. At this point the user should save all open 
files, and shutdown the computer. When utility 
power is restored the battery will recharge.
The Power On LED flashes once every second while the Back-UPS beeps once 
every second
The Back-UPS battery has 
approximately two minutes of 
remaining runtime.
The Back-UPS battery is near a total discharge 
state. At this point the user should save all open 
files, and shutdown the computer. When utility 
power is restored the battery will recharge.
The Building Wiring Fault LED illuminates
The building wiring presents a shock 
hazard that must be corrected by a 
qualified electrical.
Do not operate the Back-UPS. Call a qualified 
electrician to correct the building wiring fault.
The Back-UPS has an inadequate battery runtime
The battery is not fully charged.
The battery is near the end of useful 
life and should be replaced.
Leave the Back-UPS connected to utility power for 
16 hours while the battery charges to full capacity.
As a battery ages, the runtime capability decreases. 
Contact APC at the Web site www.apc.com, to 
order replacement batteries.
The connection from the Back-UPS to the internet is lost during a power 
outage
The modem has lost power.
Connect the modem cable into one of the Battery 
Backup + Surge Protection outlets.
LED 
Flashes
Sensitivity 
Setting
Input Voltage Range
(Utility Operation)
Recommended Use
Green
LOW
88 Vac to 142 Vac
Use this setting with equipment that is less 
sensitive to fluctuations in voltage or 
waveform distortions.
Red
MEDIUM
92 Vac to 139 Vac
Factory default setting. Use this setting 
under normal conditions.
Amber
HIGH
96 Vac to 136 Vac
Use this setting when connected equipment 
is sensitive to voltage and waveform 
fluctuations.