APC ACRC103 Manual Do Utilizador

Página de 36
15
InRow RC Installation
Stabilizing the Equipment
Floor brackets
To prevent the equipment from moving from its final location (if it is not joined with an enclosure), use 
the included bolt-down kit (AR7701). Follow the installation instructions included with the kit.
Joining to enclosures
NetShelter
 SX enclosure. 
Two 
joining brackets are installed on the front 
and rear of the equipment. Depending on 
how the holes on the joining brackets are 
used, you have the option of either 24-in 
or 600-mm spacing.
1. Remove the front and two rear 
doors from the equipment. See 
“Door removal” on page 13
2. Locate the four joining brackets 
on the equipment. Rotate each 
bracket 90° toward the adjoining 
enclosure so that the bracket is 
parallel to the floor.
3. Install the brackets using the 
Phillips screws provided with the 
equipment.
NetShelter VX enclosure. 
The equipment may be joined to a NetShelter VX enclosure (24-in spacing 
only) by using an accessory kit (AR7602), sold separately.
na
15
7
3a