APC ACRC103 Manual Do Utilizador

Página de 36
InRow RC Installation
18
Condensate pump. 
The pump is factory-wired and piped 
internally to the lower condensate pan. The pump is capable of 
moving liquid a maximum of 15.2 m (50 ft), including a 
maximum lift of 4.9 m (16 ft). For example, if your lift is 3 m 
(10 ft), you have 12.2 m (40 ft) of usable run. The pump also 
uses an on-board condensate high level float switch, which is 
wired into the InRow RC alarm input for local and remote 
alarm capabilities.
Condensate pump drain connection. 
CAUTION
CONDENSATE DAMAGE
• Do not exceed the lift or the run length of the drain system.
• To prevent equipment damage from condensate, do not leave the condensate drain line 
coiled inside the equipment. Route the condensate drain line out the top or bottom of the 
equipment before operation.
Failure to follow these instructions can result in equipment damage.
na
15
75
a
na
22
71a
Condensate drain line
Note: Sufficient PVC drain line is 
supplied to route the drain to the 
outside of the equipment. To route 
the drain line to a remote drain, 
obtain additional hardware.