3-16kVA Service Bypass Panels 
©2009 APC by Schneider Electric, APC, the APC logo, and Smart-UPS are             
owned by Schneider Electric industries S.A.S American Power Conversion  
Corporation, or their affiliated companies. All other trademarks are property 
of their respective owners. 
990-1530B
 
 
Note: Read the safety information sheet before installation.  
Illustrations in this document may differ slightly from the actual hardware. 
Attention: This product is for use in a controlled environment. Refer to product 
specifications for environmental limits. 
R
ACK 
M
OUNTING
 
 
o
 
Set SBP in the rack. If hardwiring is required, see Connecting Power 
section before screwing into the rack. 
 
 
W
ALL 
M
OUNTING
 
  
n
 
 
 
 
 
o
 
Whenever possible, attach one top screw and one bottom screw into a wall stud. If stud 
mounting is not possible, use an expandable wall anchor. Screws are not included; .25” x 
2” lag bolts are recommended. 
 
 
 T
OWER 
O
PTION 
(
FOR 
S
MART
-UPS
 
RT
 SETUPS ONLY
n
  
Remove screw from the top and bottom rear of both the UPS and SBP. Install tie 
brackets and reattach screws.
 
 
 
 
 
o
 
Unscrew and remove top cover of the 
UPS.
 
 
p
 
Attach bracket to top of UPS and SBP.
 
 
 
q
 
Reattach top cover of the UPS.
 
 
 
 
 
 
Note: The SBP5000RMI2U, when used in conjunction with an SURT3000XLI or SURT5000XLI UPS in a 
tower configuration without an external battery pack (SURT192XLBP), is suitable for mounting on 
concrete or other non-combustible smooth surfaces only.
 
 
 
U
SER 
C
ONFIGURABLE
 
Attention: When using an online UPS, put the UPS in automatic bypass mode before 
rotating the SBP switch. 
1. Normal: Power is directed from the utility outlet, through the Bypass Panel and UPS, 
and to connected equipment. For use during normal UPS operation. 
 
2. Test: Power supplied to the UPS is not output. Use when tests are being conducted on 
the UPS, and connected equipment is not yet desired. 
 
3. Bypass:
 Power from the utility outlet is filtered through the Bypass Panel, and to the 
connected equipment. Use to bypass the UPS, when functioning improperly. 
 
Note: While operating in ‘Test’ or ‘Bypass’ mode, power to the connected equipment is 
not conditioned by the UPS.  At this time, the “Equipment Protection Policy” is not valid. 
I
DENTIFYING THE 
P
ANEL 
 
Service Bypass Panels will differ. Refer to chart for unit specifications.   
Note: HW= Hardwire 
Service Bypass 
Panel 
Corresponding 
UPS Systems 
Bypass
Input 
UPS 
Input 
UPS 
Output 
PDU 
Panel 
SBP3000RM2U 
100-120V Smart-UPS 
3kVA 
L5-30P 
L5-30R 
L5-30P 
(2) 5-20R, 
(6) 5-15R 
SBP5000RMT2U 
200/208/240V  
Smart-UPS 3-4.5kVA 
L6-30P 
L6-30R 
L6-30P 
(2) L6-20R, 
(2) L6-30R 
SBP5000RMI2U
*
 
230V Smart-UPS  
3-5kVA 
C20/HW 
C19/HW 
C20/HW 
(2) C19, 
(8) C13 
SBP6KRMT2U
**
 
200/208/240V 
Symmetra 2-6kVA 
L6-30P/ 
HW 
L6-30R/ 
HW 
L6-30P/ 
HW 
(1) L6-20R, 
(2) L6-30R 
SBP6KRMI2U 
230V Symmetra  
2-6kVA 
HW 
HW 
HW 
(4) C19 
SBP3000 
100-240V Smart-UPS
3-5kVA with 30A HW
input/output 
available 
HW 
HW 
HW 
HW 
SBP10KRMT4U 
200/208/240V  
Smart-UPS RT  
7.5-10kVA 
HW 
HW 
HW 
(3) L6-20R, 
(3) L6-30R 
SBP10KRMI4U 
230V Smart-UPS RT 
7.5-10kVA 
HW (3Ph 
or 1Ph) 
HW (3Ph 
or 1Ph) 
HW 
(8) C13, 
(2) C19 
SBP16KP 
200-240V  
Symmetra LX 
4-16kVA 
HW (3Ph 
or 1Ph) 
HW (3Ph 
or 1Ph) 
HW 
HW 
SBP16KRMI4U 
220-240V  
Symmetra LX 
4-16kVA 
HW (3Ph 
or 1Ph) 
HW (3Ph 
or 1Ph) 
HW 
(3) 30A HW 
SBP16KRMP4U 
200/208/240  
Symmetra LX 
4-16kVA 
HW 
HW 
HW 
(6) L14-30R 
SBP16KRMP4U-HW 
200/208/240  
Symmetra LX 
4-16kVA 
HW 
HW 
HW 
(1) L14-30R, 
(3) L5-20R,  
(1) 100A HW 
*
For loads exceeding 3kVA, hardwiring is necessary.
 
  **
For loads exceeding 5kVA, hardwiring is necessary. 
 
 
x4
x4 
x4 
x8 
Rear
Front
x1 
x4 
x8 
x2 
x2 
x2