APC AP7900 Manual Do Utilizador

Página de 186
®
USER’S GUIDE
Switched Rack PDU
47
How to configure Device Settings
Web interface. 
Select 
Configuration 
on the 
Switched Rack PDU 
menu. 
Then, under 
Device Settings, 
click the 
Configure
 button and configure the 
Name
 and 
Location 
fields for the Rack PDU, and set the 
Coldstart Delay
.
Control console. 
1. Select 
Outlet Control/Configuration
 from the 
Device Manager
 menu. 
2. Select 
Master Control/Configuration
 from the displayed list.
3. Select 
Master Outlet Configuration 
from the next menu displayed.
4. Change the 
Name
Location
, or 
Coldstart Delay
 from this menu.
Low Load Warning 
Threshold
Set the low threshold, in amps, for the current drawn from this 
phase or bank during normal operation. A load at or below this 
level generates a warning.
Overload Outlet 
Restriction
Prevent users from applying power to outlets during an overload 
condition. You can set the following restrictions for each outlet:
None
: You can apply power to outlets regardless of an Overload 
Alarm or Near Overload Warning.
On Warning
: You cannot apply power to an outlet on the 
selected phase or bank if the current for that phase or bank has 
exceeded the Near Overload Warning threshold.
On Overload
: You cannot apply power to an outlet on the 
selected phase or bank if the current for that phase or bank has 
exceeded the Overload Alarm threshold.
Setting
Description