Lucent Technologies R5SI Manual Do Utilizador

Página de 2643
DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-218
BRI-SET, ASAI-ADJ, BRI-DAT 
10
BRI Set Audits Test (#630)
This is a series of two tests which are classified as audits. The switch sends 
messages to the BRI endpoint to perform the following tests:
Ringer Audit - This audit ensures that both the switch and the endpoint 
agree as to the current state of the endpoint’s ringer.
Lamps Audit - This audit ensures that both the switch and the endpoint 
agree as to the current state of the endpoint’s lamps.
Call Activity Audit - This audit ensures that the state of calls is consistent 
between the switch and the endpoint.
This test is not executed for ASAI or AT&T adjunct because adjuncts do not 
employ ringers or lamps, or establish calls on the B-channels associated with the 
BRI interface.
Table 10-70.
TEST #630 BRI Set Audits 
Error 
Code
Test 
Result
Description/ Recommendation
1113
ABORT
The signaling link between the switch and the endpoint 
is down.
1. Use the 
test port PCSSpp long
 command to clear 
any errors which prevent establishment of the 
signaling link.
2. Examine the results of the Signaling Link Status Test 
(#626) which is run as part of this command. If this 
test aborts or fails, follow the repair procedure for 
Test #626.
3. If the BRI Set Audits test continues to abort, escalate 
the problem.
1139
ABORT
The Packet Bus in the port network is out-of-service.
1. Follow the repair procedures for the Packet Bus.
2. After completing Step 1, execute the 
test port long 
PCSSpp
 command, and review the results of the 
BRI Port Local LAN Loop Around Test to verify the 
repair.
Continued on next page