DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-224
CABINET (Cabinet Sensors) 
10
CABINET (Cabinet Sensors)
NOTE:
CABINET is valid only in a multicarrier cabinet system. For information 
concerning single-carrier cabinet systems, refer to the DC-POWER 
(Single-Carrier Cabinet Power) Maintenance documentation.
Each multicarrier cabinet is equipped either with six non-variable speed fans or 
with six variable speed fans.
Non-Variable Speed (Standard) Fan Option.
 A non-variable speed (standard) 
fan is indicated by one of the following Product Codes: "ED67077 G1," "ED67077 
G2," or "ED67077 G3." Multicarrier cabinets with non-variable speed fans contain 
a fan speed control unit known as the AHD1 circuit pack. This circuit pack is 
designed to keep the temperature within the cabinet below 65
0
 C (149
0
 F). Air is 
drawn in by the three fans located in the front of the cabinet. The air is channeled 
upwards through a filter, then through carriers A, B, and C and out the top of the 
cabinet. Air is drawn in by the three fans located in the back of the cabinet as 
well. The air is channeled down through a filter, then through carriers D and E 
and out the bottom of the cabinet. The AHD1 circuit pack monitors five of the six 
temperature sensors located throughout the multicarrier cabinet, and it uses the 
output of these sensors to adjust fan speed and to report air flow problems. The 
Maintenance/Tape Processor in a Standard system PPN, the Duplication 
Interface circuit pack, a PPN for a High or Critical Reliability system, and the EPN 
Maintenance circuit pack in an EPN multicarrier cabinet system directly monitor 
the sixth sensor (S1) to report temperature problems. The Cabinet Sensors 
maintenance object represents the air flow and temperature problems reported 
by the AHD1 circuit pack and by the Maintenance/Tape Processor, the 
Duplication Interface circuit pack, or the EPN Maintenance circuit pack in the 
multicarrier cabinet systems.
The fans and the AHD1 circuit pack obtain their power from the -48 volt DC 
power supply of the 631 DB DC power unit in the A carrier. In a PPN cabinet for a 
High or Critical Reliability system, the 631 DB DC power unit in the B carrier can 
also provide power to the fans. The power goes from the power unit(s) to the 
1.
Where P is an appropriate port network number determined via the Port field from the 
Alarm or Error Log.
2.
If a minor alarm occurs for a variable speed fan, the fan should be checked for a dirty 
filter. If the filter is not dirty, the fan should be replaced.
MO Name As 
It Appears in 
Alarm Log
Alarm 
Level
Initial System 
Technician Command 
to Run
1
Full Name of MO
CABINET
MAJOR
test environment P 
Cabinet Sensors
CABINET
MINOR
2
test environment P 
Cabinet Sensors