DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-272
CARR-POW (Carrier Port Power Unit) for AC-Powered Systems 
10
Replacing a TN736 or TN752 Power Unit Circuit 
Pack
If the TN736 or TN752 power unit circuit pack is in a control carrier of a PPN 
system, then refer to the "Handling Control Circuit Packs" section in Chapter 5, 
"Routine Maintenance Procedures". Replacing either power unit interrupts the -5 
volt supply to the carrier. This causes all the analog circuit packs in the carrier to 
fail their Loop Around Tests and may cause failures in circuit packs in the control 
complex. After the power unit has been replaced, look for alarms against these 
maintenance objects. If ANL-LINE alarms exist, refer to Test #47 (Loop Around 
and Conference Test) in ANL-LINE Maintenance documentation. For CO-TRK 
alarms, refer to Test #33 (Loop Around and Conference Test) in CO-TRK 
Maintenance documentation.
Hardware Error Log Entries and Test to Clear 
Values
Notes:
a. Where P is an appropriate port network number taken for the PORT field of 
the Error Log.
b. Run the Power Unit Query Test (#127) first using the 
test environment P r 
2
 command. Then, if a carrier must be recycled to clear the CARR-POW 
alarm, use the 
recycle carrier PC
 command to run the Power Unit 
Recycle Test (#126). The Power Unit Recycle Test (#126) is not included 
in either the long or Short Test Sequences.
!
WARNING:
The Power Unit Recycle Test (#126) is destructive. For more 
information, refer to the description of this test.
1.
Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the 
appropriate test description and follow the recommended procedures.
Carrier Port Power Unit Error Log Entries
Error 
Type
Aux 
Data
Associated Test
Alarm 
Level
On/Off
 Board
Test to Clear Value
0
1
0
Any
Any
Any
test environment P sh r 1
1(a)(b)
0 or 1
Power Unit Query 
Test (#127)
MAJOR
ON
test environment P r 2