Maintenance Object Repair Procedures
Page 10-459
DID-TRK (DID Trunk)
10
Port Diagnostic Test (#35)
This test checks a port’s battery feed circuitry. The battery feed circuitry is tested
for on-/off-hook detection, battery shutdown, and battery reversal (WINK)
capabilities.
for on-/off-hook detection, battery shutdown, and battery reversal (WINK)
capabilities.
PASS
DID Trunk Loop Around and Conference Test is
successful. This port is functioning properly.
successful. This port is functioning properly.
1. If users are reporting troubles, examine loop
connections to the port and refer problem to the CO.
0
NO
BOARD
BOARD
The test could not relate the internal ID to the port (no
board).
board).
1. Check to ensure that the board translations are correct.
Translate the board, if necessary.
2. Issue the
busyout board
command.
3. Issue the
reset board
command.
4. Issue the
release busy board
command.
5. Issue the
test board
command. This should
re-establish the linkage between the internal ID and the
port.
port.
Table 10-126.
TEST #35 Port Diagnostic Test
Error
Code
Test
Result
Description/ Recommendation
ABORT
System resources required to run this test were not
available.
available.
1. Retry the command at 1-minute intervals a maximum
of 5 times.
2. If the test continues to abort, escalate the problem.
Continued on next page
Table 10-125.
TEST #33 Loop Around and Conference
Circuit Test —
Continued
Error
Code
Test
Result
Description/ Recommendation
Continued on next page