Maintenance Object Repair Procedures
Page 10-906
MIS (Management Information System)
10
MIS (Management Information
System)
System)
The Management Information System (MIS)/Call Management System (CMS) MO
is used only for administering MIS translations, such as trunks and stations.
There are no hardware failures associated with this MO.
is used only for administering MIS translations, such as trunks and stations.
There are no hardware failures associated with this MO.
NOTE:
To diagnose MIS link hardware errors and alarms, see PI-LINK (Processor
Interface Link) and PI-SCI (System Communication Interface) maintenance
information.
To diagnose MIS link hardware errors and alarms, see PI-LINK (Processor
Interface Link) and PI-SCI (System Communication Interface) maintenance
information.
The MIS/CMS is an adjunct processor that collects ACD data sent from the
system. To change MIS translations, a system administrator must first enter a
system. To change MIS translations, a system administrator must first enter a
busyout mis
command at the terminal. When the MIS is busied out, the system
stops sending ACD data to the MIS, and a Warning alarm is raised. When
finished, a
finished, a
release mis
command should be entered at the terminal. This clears
the Warning alarm and allows the switch to send ACD data to the MIS.
Error Log Entries and Test to Clear Values
Note:
a. When the
busyout MIS
command is issued, no data is sent to the
MIS/CMS regardless of the link state. To allow data to be sent to MIS/CMS,
a
a
release mis
command must be issued from the terminal.
1.
Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
appropriate test description and follow the recommended procedures.
MO Name (In
Alarm Log
Alarm
Level
Initial Command to
Run
Full Name of MO
MIS
WRN
release mis
Management Information System
Table 10-259.
Management Information System Error Log Entries
Error
Type
Type
Aux
Data
Associated Test
Alarm Level
On/Off
Board
Test to Clear Value
0
1
0
Any
Any
Any
release mis
18(a)
0
busyout mis
WARNING
ON
release mis
Continued on next page