Maintenance Object Repair Procedures 
Page 10-956
M/T-ANL (Maintenance/Test Analog Port) 
10
Analog Port Digital Loop Around Test (#13)
This test is a modification of the Voice and Control Channel Local Loop Test used 
by Digital Station (DIG-LINE) maintenance. This test does not perform the control 
channel and secondary information channel loop around tests as described for 
DIG-LINE, as these data paths do not exist for the Maintenance/Test Analog Port. 
The primary information channel is tested by first looping back the data channel 
onto the TDM Bus, and then sending a digital count from the Tone-Clock circuit 
pack and receiving the same digital count with a general purpose tone detector. 
A conference test is done next for the primary information channel. This test is the 
same as Conference Test (#6).
Only one value (Pass, Fail, or Abort) is generated as a result of the two tests. If 
either fails or aborts, the sequence is stopped
Table 10-274.
TEST #13 Analog Port Digital Loop Around Test 
Error 
Code
Test 
Result
Description/ Recommendation
ABORT
Internal System Error
1. Retry the command at 1 minute intervals a maximum 
of 3 times.
2. If the test continues to abort, escalate the problem.
1000
ABORT
The port is in use on a valid ATMS Test Call.
1. Retry the command at 1 minute intervals a maximum 
of 3 times.
2. If the test continues to abort and the port is not in 
use on a valid ATMS Test Call, escalate the problem. 
To determine whether the port is in use by an ATMS 
Test Call enter 
status station ext
 where 
ext
 is the 
assigned ATMS station number.
1001
ABORT
System resources required to run this test are not 
available.
1. Retry the command at 1 minute intervals a maximum 
of 3 times.
2. If the test continues to abort, escalate the problem.
Continued on next page