DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si  
555-230-123  
Issue 1
April 1997
Maintenance Commands and Trouble-Clearing Aids 
Page 8-157
download update-file 
8
If an update file which is created for a different system (i.e.,. a patch file is 
created for a tape system and downloaded to a flash system), the following 
message is displayed:
Update file designed for a different configuration, file will not be used
If the update file is too large to fit in the remaining space, the following message 
is displayed:
Update file is too large to fit on device
If the calculated file checksum is incorrect, the following message will be 
displayed:
File checksum failed; file will not be used
If an invalid update file block was found, the following message will be displayed:
Found a bad file block; file will not be used
If the total number of blocks listed in the header block of the update file did not 
match the number of blocks received by the SPE, the following message is 
displayed:
Received an invalid number of blocks; file will be ignored
The total number of subpatches listed in the header of the update file did not 
match the number of subpatches received by the switch
Received wrong number of subpatches for update file
Output
None
Feature Interactions
The form displayed for the list configuration software-vintage command has been 
modified to reflect the changes imposed by the flash architecture. The 
list 
configuration software
 command should allow INADS to determine, with one 
query, the hardware configuration, software vintage and patch identifier.
There is no interaction with routine periodic or scheduled maintenance because 
patches are only applied on restarts before the system is in normal operation.
The flash checksum test acts as a backup check to make sure the entire field 
update file was applied correctly. It can fail because of a bad checksum update 
from a poorly constructed update file or because the patching operation has 
aborted. When the flash Checksum Test fails, a MAJOR on-board alarm is raised 
on the processor/memory circuit pack. Maintenance runs a data consistency test 
on a daily basis to check that copies of translations, announcements and 
software files are consistent across both processors in a High or Critical