8.4 Installation
Installation specifications
Table 8.3
Expansion Disk Cabinet Installation Specifications (1)
Item
Specification
Mass
Up to 38kg
Power condition
Input voltage
Single phase
 100 to 120 VAC
(+-10%) 
Single phase
 200 to 240 VAC
(+-10%) 
Input frequency
50/60 Hz (+2 to -4%)
Maximum consumption current
3 A
Leakage current(1 for each cable)
1.2 mA or less
1.5 A
2.7 mA or less
Ground resistance
100ohm or less ( class C installation standard)
Temperature condition Operating
5 to 35 degrees Celsius (+41 to +95 F) (*1)
Not operating
0 to 50 degrees Celsius (+32 to +122F)
Humidity condition
Operating
20 to 80%RH (no condensation)
Not operating
8 to 80% RH (no condensation)
Vibrations condition
Operating
0.2 G
Idle
0.4 G
Noise
47 db (A) (*2)
Installation
Standalone type
*1:
If the ambient temperature exceeds 35 degrees Celsius (+95F) during operation, a
warning message is displayed. Take steps to rectify the problem immediately.
*2:
The indicated noise is the mean value of the measurements obtained in an anechoic
chamber with less echoic influence. The actual noise measured at the installation site
may be greater than the indication noise due to surrounding noise and echoes.