Omron C200HE Manual Do Utilizador

Página de 564
334
S
Function
Word
address
The contents of S through S+4 are copied to the part of the PC Setup
that contains the settings for the port specified by N.
Constant
(#0000)
The settings for the port specified by N are returned to their default val-
ues.
Application Example
This example shows a program that transfers the contents of DM 0100 through
DM 0104 to the PC Setup area for Communications Board port A (DM 6555
through DM 6569).
@STUP(––)
001
DM 0100
000
00000
Address
Instruction
Operands
00000
LD
00000
00001
@STUP(––)
001
DM
0100
000
The settings are transferred as shown below. The Changing RS-232C Setup
Flag (SR 27504) will be turned OFF when the transfer has been completed.
DM 0100
DM 0101
DM 0102
DM 0103
DM 0104
1001
DM 6555
0803
DM 6556
0000
DM 6557
2000
DM 6558
0000
DM 6559
1001
0803
0000
2000
0000
1001
0803
0000
2000
0000
1001
0803
0000
2000
0000
1001
0803
0000
2000
0000
1001
0803
0000
2000
0000
1001
0803
0000
2000
0000
1001
0803
0000
2000
0000
(Refer to 3-6-4 PC Setup
for details.)
The following table shows the function of the transferred setup data.
Word
Content
(see note)
Function
DM 0100
1001
Enables the communications settings in DM 0101 and
sets the communications mode to RS-232C.
DM 0101
0803
Sets the following communications settings:
9,600 bps, 1 start bit, 8-bit data, 1 stop bit, no parity
DM 0102
0000
No transmission delay (0 ms)
DM 0103
2000
Enables the end code CR, LF.
DM 0104
0000
---
Note For details on the contents of setup data, refer to 3-6-4 PC Setup.
Flags
ER:
Indirectly addressed DM word is non-existent. (Content of 
DM word is
not BCD, or the DM area boundary has been exceeded.)
The port specifier (N) isn’t IR 000, IR 001, or IR 002.
Port A has been specified, but pin 2 of the DIP switch is ON.
The PC Setup is write-protected. (Pin 1 of the DIP switch is ON.)
The specified source words exceed the data area.
The instruction was executed from an interrupt program.
Serial Communications Instructions
Section 5-27