Siemens S7 300 (ISO TCP) 
HMI Factory Setting: 
IP Address: 192.168.0.1 
COM Port: 102 
Control Area / Status Area: DBW0 / DBW20 
 
Connection  
Standard Jumper Cable / Network Cable without jumper (Auto-detected by HMI) 
 
Definition of PLC Read/Write Address 
a. Registers  
Format 
Type 
Word No.(n) 
Bank No.(m) 
Read/Write Range 
Data Length
Note 
IWn 
IW0 – IW65534 Word 
 
Input Image 
IDn 
ID0 – ID65532 Double 
Word  
QWn 
QW0 – QW65534 Word  
Output Image 
QDn 
QD0 – QD65532 Double 
Word  
MWn 
MW0 – MW65534 Word  
Internal Bits 
MDn 
MD0 – MD65532 Double 
Word  
DBm.DBWn 
DB1.DBW0 –   
DB255.DBW65534 
Word 
Data Area 
DBm.DBDn 
DB1.DBD0 –   
DB255.DBW65532 
Double Word
DBWn 
DBW0 – DBW65534 Word   
DBDn 
DBD0 – DBD65532 Double 
Word  
VWn 
VW0 – VW65534 Word  
Data Area (DB10) 
VDn 
VD0 – VD65532 Double 
Word  
Timer 
Tn 
T0 – T65535 Word 
Counter 
Cn 
C0 – C65535 Double 
Word