Chaparral G5312/G7313 Manual Do Utilizador

Página de 160
 
Configuring the Controller
7-19
To enable or disable the alarm:
1
From the System Menu, select Configuration Menu and press Enter.
The Configuration Menu screen displays. 
2
Select Alarm Mute and press Enter.
The Alarm Mute screen displays. The current setting is marked with an * next 
to it.
3
Select the option you want and press Enter.
VCC voltage
Warning—5V -3.5% and +6.5%
Shutdown—5V -6.5% and +10%
!
Check the 
Disk Array
 Administrator software to 
!
If it is a warning alarm, let the controller 
continue to operate.
!
If it is a shutdown alarm, turn off the power to 
the controller and send it for service.
12V voltage
Warning—12V -8% and +8%
Shutdown—12V -10% and +10%
!
Same as above for the VCC voltage.
Table 7-1. Alarm thresholds
Alarm threshold
What to do when the alarm sounds