be cycled on the device to return it to its default state.  Otherwise, 
if 0 or 1 is entered it will be ignored and the device will remain in 
its last override state.  Refer to Section 4.2.2 for connection 
details. 
6.4  SDM-CVO4 Instruction Example 
This program example is for a weather station measuring wind speed, wind 
direction, temperature, and relative humidity.  Each parameter is scaled to 0 to 
10000 mVDC, and output to a SCADA system through the SDM-CVO4.  
Public WS_ms 
Public WD_0_360 
Public Temp_C 
Public RH 
Public WD_0_540 
Public Flag 
Public CVO4Output(4) 
Alias CVO4Output(1) = WSOut 
Alias CVO4Output(2) = WDOut 
Alias CVO4Output(3) = TempOut 
Alias CVO4Output(4) = RHOut 
 
'Code for DataTable OneMin 
DataTable(OneMin,1,-1) 
 DataInterval(0,1,Min,0) 
 
WindVector (1, WS_ms,WD_0_360, IEEE4, 0, 0, 0, 0) 
 Average(1,Temp_C,IEEE4,0) 
 Sample(1,RH, 
IEEE4) 
EndTable 
 
BeginProg 
 Scan(1,Sec,1,0) 
 
 
' Code for 03001 wind measurements, WS_ms & WD_0_360: 
 
PulseCount(WS_ms, 1, 1, 1, 1, 0.75, 0.2) 
 
 
BrHalf(WD_0_360, 1,mV1000, 1, 1, 1, 1000, True, 1000, 250, 355, 0) 
 
 
' Code for CS500 measurement, AirTC and RH: 
  VoltSE(Temp_C,1,mV1000,3,0, 
0, 
_60Hz,0.1,-40.0) 
 
 
VoltSE(RH,1,mV1000,2,0, 0, _60Hz,0.1, 0) 
 
 
' Call Data Table 
  CallTable(OneMin) 
 
 
' Convert 0-360 WD to 0-540: 
 
 
If WD_0_540 >= 270 and WD_0_360 <180 Then 
 
 
 
WD_0_540 = WD_0_360 + 360 
 
 
Else 
   WD_0_540 
WD_0_360 
 